Inspections for the day of: Monday, January 9, 2006.
Number of inspections: 9
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR05-00803 INSP-Alarm Testing1/6/20061/9/20061/10/2006 8:40:33 AMPFAIL
Duplicate inspection request for the fire sprinkler permit, field installation does not reflect the approved plan to a significant degree which shall require resubmittal for verification and approval of the modifications prior to final field inspection.
FIR05-00803 INSP-Final Inspection1/6/20061/9/20061/10/2006 8:29:33 AMPFAIL
The fire sprinkler field installation does not reflect the approved plan to a significant degree which shall require resubmittal for verification and approval of the modifications prior to final field inspection.
BLD05-02317 FIRE-Final Inspection1/9/20061/9/20061/10/2006 8:18:39 AMPDEFR
wip
FIR05-00849 INSP-Final Inspection1/9/20061/9/20061/10/2006 8:17:05 AMPPASS
Items on c/n have been completed and retested, fire alarm passed final inspection.
FIR05-00802 INSP-Final Inspection1/6/20061/9/20061/10/2006 8:11:36 AMPFAIL
One strobe notification device failed to function properly during testing, the two fan coil unit duct smoke detectors tested okay.
FIR05-00425 INSP-Sprinkler Rough-in/Hydro1/6/20061/9/20061/10/2006 8:01:32 AMAPART
Overhead hydrostatic test for the dry systems on levels 2, 3 and 4 passed inspection.
BLD04-00947 FIRE-Sprinkler Rough-in1/6/20061/9/20061/9/2006 11:08:45 AMAPART
Inspection for tenting at fire sprinklers good for cover at 3rd floor apt. A east only, the remaining 3 units on the floor not complete at this time.
BLD04-02056 FIRE-Final Inspection1/9/20061/9/20061/9/2006 10:18:02 AMPFAIL
Need to provide a fire extinguisher for the second level in the common stairway, remove dust covers from smoke alarms, remove tape and paper at the fire sprinkler heads and a/v in the common stairway.
FIR05-00442 INSP-Final Inspection1/6/20061/9/20061/9/2006 10:14:19 AMAPASS
Fire sprinkler passed final inspection, will verify tape and paper at heads in the common stairway have been removed at BLD final.