Inspections for the day of: Tuesday, January 9, 2007.
Number of inspections: 16
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR06-00830 INSP-Final Inspection1/9/20071/9/20071/9/2007 5:37:42 PMPCANC
to be rescheduled
FIR06-00698 INSP-Supply line flush1/8/20071/9/20071/9/2007 5:37:06 PMPPASS
Underground flush passed.
FIR06-00631 INSP-Sprinkler Rough-in/Hydro1/8/20071/9/20071/9/2007 3:09:05 PMPCANC
To be rescheduled
FIR06-00977 INSP-Sprinkler Rough-in/Hydro1/8/20071/9/20071/9/2007 2:50:10 PMPPART
The second floor wet and dry systems were the only areas inspected today. Two uprights are blocked by duct and webbing. The uprights on the dry system need to be aligned with the slope of the roof deck and then there is the insulation issue that needs to be corrected. Also the branchline over the elevator shaft has not been installed.
FIR06-00971 INSP-Final Inspection1/5/20071/9/20071/9/2007 1:51:06 PMPPASS
permit finaled
FIR06-00564 INSP-Conference1/8/20071/9/20071/9/2007 1:49:20 PMADONE
I went over life safety issues with John. Exit discharge lighting will be required and the two doors behind the platform can remain as long as all hardware is removed and the doors are covered/blocked from view.
FIR06-00698 INSP-Sprinkler Rough-in/Hydro1/8/20071/9/20071/9/2007 11:35:19 AMAPASS
Underground hydro passed.
MIS07-00005 FIR-Final1/8/20071/9/20071/9/2007 10:07:03 AMAPASS
life safety finaled
MIS07-00004 FIR-Final1/8/20071/9/20071/9/2007 9:05:17 AMAPASS
Life safety passed.
BLD06-01569 FIRE-Final Inspection1/8/20071/9/20071/9/2007 8:45:12 AMACANC
Phone #: ###-#### Inspection cancelled from web by: Todd Kurns
BLD06-01568 FIRE-Final Inspection1/8/20071/9/20071/9/2007 8:45:00 AMACANC
Phone #: ###-#### Inspection cancelled from web by: Todd Kurns
BLD06-01567 FIRE-Final Inspection1/8/20071/9/20071/9/2007 8:44:50 AMACANC
Phone #: ###-#### Inspection cancelled from web by: Todd Kurns
BLD06-01566 FIRE-Final Inspection1/8/20071/9/20071/9/2007 8:44:37 AMACANC
Troy, Please call me when you are on your way. Thanks, Todd Phone #: ###-#### Inspection cancelled from web by: Todd Kurns
BLD06-02339 FIRE-Final Inspection1/8/20071/9/20071/9/2007 8:43:48 AMAFAIL
The fire alarm system needs to be modified such as overspaced a/v in the north side of the tenant space and no a/v in the breakroom. Other life safety items appear ok.
FIR06-00792 INSP-Final Inspection1/8/20071/9/20071/9/2007 8:33:24 AMAPASS
permit finaled
BLD06-01466 FIRE-Final Inspection1/9/20071/9/20071/9/2007 12:00:00 AMPCANC
dan; Phone #: ###-#### Internet Inspection Request from: Victoria Beall