Inspections for the day of: Friday, January 9, 2009.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR08-00270 INSP-Sprinkler Rough-in/Hydro1/8/20091/9/20091/13/2009 5:22:40 PMAPART
See inspection comments 1/13.
FIR08-00018 INSP-Sprinkler Rough-in/Hydro1/8/20091/9/20091/12/2009 5:07:19 PMAPART
10th floor rough-in appears acceptable pending verification as-built plans match approved resubmittals for field modifications. 5th floor corridor cover inspection failed due to two overspaced pendent heads and one missed obstruction.
FIR08-00801 INSP-Supply line flush1/8/20091/9/20091/9/2009 6:32:10 PMPPART
UG fire supply line hydrostatic test passed. Also okayed UG install for bury.
BLD06-01451 FIRE-Conference1/8/20091/9/20091/9/2009 6:30:04 PMADONE
Regarding pin up insulation at the garage levels adjacent to sprinkler uprights.
FIR08-00424 INSP-Conference1/9/20091/9/20091/9/2009 6:28:43 PMPDONE
Regarding project completion schedule.
FIR08-00676 FIR-Aging Inspection1/9/20091/9/20091/9/2009 12:10:51 PM DEFR
In progress
FIR08-00723 INSP-Final Inspection1/8/20091/9/20091/9/2009 12:06:35 PMAPASS
Site testing passed, fire alarm permit finaled.
BLD08-01434 FIRE-Final Inspection1/8/20091/9/20091/9/2009 10:19:11 AMAPASS
Items on C/N completed, fire life safety passed.
FIR08-00739 INSP-Final Inspection1/9/20091/9/20091/9/2009 10:18:30 AMAPASS
Fire alarm permit finaled.
FIR08-00739 INSP-Alarm Testing1/8/20091/9/20091/9/2009 10:17:57 AMAPASS
Necessary repairs have been made, battery power fire alarm testing passed.
BLD08-02129 FIRE-Final Inspection1/8/20091/9/20091/9/2009 10:13:53 AMAPART
Final pending completion of work at leasable work space 400 and installation of correct directional arrow exit signs.