Inspections for the day of: Thursday, January 9, 2014.
Number of inspections: 5
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR14-00018 INSP-Sprinkler Rough-in/Hydro1/8/20141/9/20141/9/2014 3:46:42 PMAPASS
Underground hydro test passed.
FIR14-00018 INSP-Supply line flush1/8/20141/9/20141/9/2014 3:23:16 PMAPASS
Underground flush passed
FIR13-00690 INSP-Sprinkler Rough-in1/8/20141/9/20141/9/2014 1:51:55 PMAPASS
See the city approved plans for locations where piping can be covered marked in red.
FIR13-00712 INSP-Sprinkler Rough-in1/8/20141/9/20141/9/2014 1:50:42 PMAPART
Piping installation passed but round duct work installed below the ceiling is causing obstructions. Don and I went over the "three times rule" in NFPA 13. He is going to modify the installation.
BLD13-03567 FIRE-Final Inspection1/9/20141/9/20141/9/2014 1:48:59 PMPPASS
Life safety passed