ELE17-03981
| Final | 1/9/2018 | 1/9/2018 | 1/9/2018 1:54:52 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Bob Glenn Final ok
|
ELE16-03931
| Final | 1/9/2018 | 1/9/2018 | 1/9/2018 12:16:36 PM | A | PART |
|
|
units 701,702,704 through 709, 721,722 Phone #: ###-#### Inspection requested via web by Cathy Duchek Added 711, 712, 713 to list of rooms, Units signed off in office. Partial final ok.
|
ELE16-03932
| Final | 1/9/2018 | 1/9/2018 | 1/9/2018 11:32:08 AM | A | PART |
|
|
units 624, 630 Phone #: ###-#### Inspection requested via web by Cathy Duchek Corrections complete 624 water heater and 630 bath GFI Partial final ok
|
ELE18-00044
| Electrical Rough-In | 1/8/2018 | 1/9/2018 | 1/9/2018 10:16:36 AM | A | PASS |
|
|
Please contact Geoff Hannaford at ###-#### for exact location. capitol ; main. thank you Phone #: ###-#### Inspection requested via web by Debby Pierce Under ground just east of 746 main entrance rough in ok cover
|
ELE18-00070
| Rough-In Permanent Service | 1/8/2018 | 1/9/2018 | 1/9/2018 9:44:41 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Darryn Coburn Rough in ok cover p/s u/g n ok
|
ELE18-00080
| Temporary Service | 1/8/2018 | 1/9/2018 | 1/9/2018 9:04:19 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Bob Glenn t/s u/g n ok
|
ELE17-03981
| Final | 1/8/2018 | 1/9/2018 | 1/9/2018 8:56:24 AM | A | FAIL |
|
|
CODES 1234 Phone #: ###-#### Inspection requested via web by Bob Glenn 110.3- Master bath GFI not fully tripping out. 406.6 Receptacle Faceplates (Cover Plates). Receptacle faceplates shall be installed so as to completely cover the opening and seat against the mounting surface. Kitchen
|