Inspections for the day of: Tuesday, January 9, 2018.
Number of inspections: 7
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE17-03981 Final1/9/20181/9/20181/9/2018 1:54:52 PMPPASS
Phone #: ###-#### Inspection requested via web by Bob Glenn
Final ok
ELE16-03931 Final1/9/20181/9/20181/9/2018 12:16:36 PMAPART
units 701,702,704 through 709, 721,722 Phone #: ###-#### Inspection requested via web by Cathy Duchek
Added 711, 712, 713 to list of rooms, Units signed off in office. Partial final ok.
ELE16-03932 Final1/9/20181/9/20181/9/2018 11:32:08 AMAPART
units 624, 630 Phone #: ###-#### Inspection requested via web by Cathy Duchek
Corrections complete 624 water heater and 630 bath GFI Partial final ok
ELE18-00044 Electrical Rough-In1/8/20181/9/20181/9/2018 10:16:36 AMAPASS
Please contact Geoff Hannaford at ###-#### for exact location.
capitol ; main. thank you Phone #: ###-#### Inspection requested via web by Debby Pierce
Under ground just east of 746 main entrance rough in ok cover
ELE18-00070 Rough-In Permanent Service1/8/20181/9/20181/9/2018 9:44:41 AMAPASS
Phone #: ###-#### Inspection requested via web by Darryn Coburn
Rough in ok cover p/s u/g n ok
ELE18-00080 Temporary Service1/8/20181/9/20181/9/2018 9:04:19 AMAPASS
Phone #: ###-#### Inspection requested via web by Bob Glenn
t/s u/g n ok
ELE17-03981 Final1/8/20181/9/20181/9/2018 8:56:24 AMAFAIL
CODES 1234 Phone #: ###-#### Inspection requested via web by Bob Glenn
110.3- Master bath GFI not fully tripping out.
406.6 Receptacle Faceplates (Cover Plates). Receptacle faceplates shall be installed so as to completely cover the opening and seat against the mounting surface. Kitchen