ELE17-04160
| Permanent Service | 1/9/2018 | 1/9/2018 | 1/9/2018 2:12:23 PM | P | PASS |
|
|
200 amp pedestal Phone #: ###-#### Inspection requested via web by jamie berg...p/s u/g new ok
|
ELE17-03465
| Electrical Rough-In | 1/8/2018 | 1/9/2018 | 1/9/2018 2:11:42 PM | A | PASS |
|
|
Ceiling inspection for cover. I will be onsite by 9am. Phone #: ###-#### Inspection requested via web by Sean Patton...hard lid area, vapor barrier ceiling areas, water fountain in existing tennant space and exterior walls only
|
ELE17-04162
| Permanent Service | 1/9/2018 | 1/9/2018 | 1/9/2018 1:53:56 PM | P | FAIL |
|
|
200 amp pedestal Phone #: ###-#### Inspection requested via web by jamie berg.. 1) bonding of two haves needs installed 2) grounding electrode wire needs hooked up at service
|
ELE17-03993
| Final | 1/9/2018 | 1/9/2018 | 1/9/2018 1:20:39 PM | P | PASS |
|
|
Customer Back Filled Trenches after being told not to. Phone #: ###-#### Inspection requested via web by Pat Marvin...trench depth verified by pictures, UL listed equipment, OCPD ok to final
|
ELE17-04221
| Final | 1/9/2018 | 1/9/2018 | 1/9/2018 12:43:26 PM | P | PASS |
|
|
Please final after rough in inspection this permit was for outside soffit lighting for the property management and is not part of the store remodel thx Phone #: ###-#### Inspection requested via web by David Feller...job complete..ok to final
|
ELE17-04221
| Electrical Rough-In | 1/9/2018 | 1/9/2018 | 1/9/2018 12:42:53 PM | P | PASS |
|
|
Exterior soffit lighting repair and LED retrofit replace lenses By passed Ballast wiring Phone #: ###-#### Inspection requested via web by David Feller...UL lamps installed in fixtures
|
ELE17-04087
| Rough-In Permanent Service | 1/8/2018 | 1/9/2018 | 1/9/2018 12:07:24 PM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Todd Hall...rough in ok to cover...p/s u/g new ok 5 meters
|
ELE17-03418
| Final | 1/8/2018 | 1/9/2018 | 1/9/2018 11:26:08 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Todd Hall...ok to final
|
ELE17-04199
| Electrical Rough-In | 1/8/2018 | 1/9/2018 | 1/9/2018 10:52:39 AM | A | PASS |
|
|
Pls contact Bryce (Foreman) @ ###-#### or George (Electrician) @ ###-#### one hr prior or if you have any questions. Thank you. Inspection requested via web by Christian Kilpatrick...UL listing verified, plans onsite
|
ELE17-03598
| Final | 1/8/2018 | 1/9/2018 | 1/9/2018 9:29:57 AM | A | PASS |
|
|
Inspection requested via web by A.M.E. Office..ok to final
|
ELE17-02138
| Final | 1/8/2018 | 1/9/2018 | 1/9/2018 9:13:04 AM | A | PASS |
|
|
garage code 0813 Phone #: ###-#### Inspection requested via web by cal crosby...ok to final
|
ELE17-03820
| Final | 1/8/2018 | 1/9/2018 | 1/9/2018 8:29:01 AM | A | PASS |
|
|
200 amp pedestal Phone #: ###-#### Inspection requested via web by jamie berg...ok to final
|
ELE13-03204
| Final | 1/9/2018 | 1/9/2018 | 1/9/2018 7:58:39 AM | A | PASS |
|
|
no corrections needed...ok to final
|
ELE13-03204
| ELE-Aging Inspection | 1/9/2018 | 1/9/2018 | 1/9/2018 7:58:11 AM | | DONE |
|
|
final scheduled
|