Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR17-00305 INSP-Sprinkler Rough-in1/8/20181/9/20181/9/2018 2:54:46 PMPPART
Piping above the lay-in ceilings is ok to cover. Sprinkler coverage is required under the overhead door. Also the dry sidewall heads on under the east canopy are less than 4" from the underside of the soffit.
BLD17-04485 FIRE-Final Inspection1/9/20181/9/20181/9/2018 12:20:52 PMPPASS
life safety passed

Sid Phone #: ###-####
NAF17-00091 INSP-Sprinkler Rough-in1/8/20181/9/20181/9/2018 10:20:10 AMAPASS
The underground supply line rough-in passed. Piping can be covered.
BLD17-01063 FIRE-Final Inspection1/8/20181/9/20181/9/2018 9:44:04 AMAFAIL
Provide a tagged fire extinguisher as discussed and a racking permit for the storage rack within the building.

Phone #: ###-#### Inspection requested via web by Ryan Steinwand
FIR17-00411 INSP-Final Inspection1/9/20181/9/20181/9/2018 9:17:41 AMPPASS
Permit finaled
BLD16-04310 FIRE-Final Inspection1/9/20181/9/20181/9/2018 9:17:26 AMPPASS
Life safety passed.

Phone #: ###-#### Inspection requested via web by David Scaggs
BLD16-04310 FIRE-Final Inspection1/9/20181/9/20181/9/2018 8:03:55 AMPCANC
Phone #: ###-#### >> Inspection requested via web by David Scaggs Inspection cancelled from web by: David Scaggs