FIR17-00730
| INSP-Sprinkler Rough-in/Hydro | 1/9/2018 | 1/9/2018 | 1/9/2018 2:23:16 PM | P | PASS |
|
|
Rough in inspection for overhead fire sprinkler piping on level 1 and basement level complete.
|
FIR17-00726
| INSP-Final Inspection | 1/9/2018 | 1/9/2018 | 1/9/2018 2:22:45 PM | P | PASS |
|
|
Final inspection for underground supply and remote FDC complete.
|
FIR17-00726
| INSP-Sprinkler Rough-in/Hydro | 1/9/2018 | 1/9/2018 | 1/9/2018 2:21:48 PM | P | DONE |
|
|
Hydrostatic test for underground supply and remote FDC witnessed, no observed pressure loss at riser gauge.
|
FIR17-00730
| INSP-Sprinkler Rough-in/Hydro | 1/9/2018 | 1/9/2018 | 1/9/2018 2:19:46 PM | P | DONE |
|
|
Hydrostatic test for basement overhead fire sprinkler piping witnessed, no observed pressure loss at riser gauge.
|
FIR17-00657
| INSP-Sprinkler Rough-in/Hydro | 1/8/2018 | 1/9/2018 | 1/9/2018 1:43:34 PM | P | DONE |
|
|
Hydrostatic test for TI overhead fire sprinkler piping witnessed, no observed pressure loss at riser gauge.
|
BLD16-03767
| FIRE-Final Inspection | 1/8/2018 | 1/9/2018 | 1/9/2018 10:44:29 AM | A | FAIL |
|
|
Appears that walls have been added since last fire sprinkler modification, Fire sprinklers need to be added in lowered ceiling by restroom and main entry to space. Fire sprinkler in storage room and wall by main entry are to close to wall.
|
BLD17-02139
| FIRE-Final Inspection | 1/8/2018 | 1/9/2018 | 1/9/2018 10:29:04 AM | A | PASS |
|
|
No fire sprinklers, no fire alarms, commercial kitchen hood fire suppression system inspection complete, fire extinguishers are in place with current inspection tags. Final life fire safety inspection for area of work complete.
|
FIR17-00706
| INSP-Sprinkler Rough-in | 1/8/2018 | 1/9/2018 | 1/9/2018 10:23:33 AM | A | PART |
|
|
Rough in inspection for overhead fire sprinkler piping on level 1 level and mezzanine level on level 1 complete.
|
BLD15-01134
| FIRE-Final Inspection | 1/8/2018 | 1/9/2018 | 1/9/2018 9:46:31 AM | A | PASS |
|
|
No fire sprinklers, smoke detectors are stand-alone, fire extinguishers are mounted under kitchen sink. Final life fire safety inspection complete.
|
BLD16-01606
| FIRE-Final Inspection | 1/8/2018 | 1/9/2018 | 1/9/2018 9:46:18 AM | A | PASS |
|
|
No fire sprinklers, smoke detectors are stand-alone, fire extinguishers are mounted under kitchen sink. Final life fire safety inspection complete.
|
BLD15-01132
| FIRE-Final Inspection | 1/8/2018 | 1/9/2018 | 1/9/2018 9:46:05 AM | A | PASS |
|
|
No fire sprinklers, smoke detectors are stand-alone, fire extinguishers are mounted under kitchen sink. Final life fire safety inspection complete.
|
BLD16-01600
| FIRE-Final Inspection | 1/8/2018 | 1/9/2018 | 1/9/2018 9:45:51 AM | A | PASS |
|
|
No fire sprinklers, smoke detectors are stand-alone, fire extinguishers are mounted under kitchen sink. Final life fire safety inspection complete.
|
BLD16-01601
| FIRE-Final Inspection | 1/8/2018 | 1/9/2018 | 1/9/2018 9:45:35 AM | A | PASS |
|
|
No fire sprinklers, smoke detectors are stand-alone, fire extinguishers are mounted under kitchen sink. Final life fire safety inspection complete.
|
BLD16-01602
| FIRE-Final Inspection | 1/8/2018 | 1/9/2018 | 1/9/2018 9:45:11 AM | A | PASS |
|
|
No fire sprinklers, smoke detectors are stand-alone, fire extinguishers are mounted under kitchen sink. Final life fire safety inspection complete.
|
BLD17-00616
| FIRE-Final Inspection | 1/8/2018 | 1/9/2018 | 1/9/2018 8:37:08 AM | A | FAIL |
|
|
Replace concealed fire sprinkler escutcheons that were painted after installation. Provide fire sprinkler in data closet.
|