Inspections for the day of: Tuesday, January 9, 2018.
Number of inspections: 15
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJim Page
TitleFIRE INSPECTOR
Phone #208-914-5431
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR17-00730 INSP-Sprinkler Rough-in/Hydro1/9/20181/9/20181/9/2018 2:23:16 PMPPASS
Rough in inspection for overhead fire sprinkler piping on level 1 and basement level complete.
FIR17-00726 INSP-Final Inspection1/9/20181/9/20181/9/2018 2:22:45 PMPPASS
Final inspection for underground supply and remote FDC complete.
FIR17-00726 INSP-Sprinkler Rough-in/Hydro1/9/20181/9/20181/9/2018 2:21:48 PMPDONE
Hydrostatic test for underground supply and remote FDC witnessed, no observed pressure loss at riser gauge.
FIR17-00730 INSP-Sprinkler Rough-in/Hydro1/9/20181/9/20181/9/2018 2:19:46 PMPDONE
Hydrostatic test for basement overhead fire sprinkler piping witnessed, no observed pressure loss at riser gauge.
FIR17-00657 INSP-Sprinkler Rough-in/Hydro1/8/20181/9/20181/9/2018 1:43:34 PMPDONE
Hydrostatic test for TI overhead fire sprinkler piping witnessed, no observed pressure loss at riser gauge.
BLD16-03767 FIRE-Final Inspection1/8/20181/9/20181/9/2018 10:44:29 AMAFAIL
Appears that walls have been added since last fire sprinkler modification, Fire sprinklers need to be added in lowered ceiling by restroom and main entry to space. Fire sprinkler in storage room and wall by main entry are to close to wall.
BLD17-02139 FIRE-Final Inspection1/8/20181/9/20181/9/2018 10:29:04 AMAPASS
No fire sprinklers, no fire alarms, commercial kitchen hood fire suppression system inspection complete, fire extinguishers are in place with current inspection tags. Final life fire safety inspection for area of work complete.
FIR17-00706 INSP-Sprinkler Rough-in1/8/20181/9/20181/9/2018 10:23:33 AMAPART
Rough in inspection for overhead fire sprinkler piping on level 1 level and mezzanine level on level 1 complete.
BLD15-01134 FIRE-Final Inspection1/8/20181/9/20181/9/2018 9:46:31 AMAPASS
No fire sprinklers, smoke detectors are stand-alone, fire extinguishers are mounted under kitchen sink. Final life fire safety inspection complete.
BLD16-01606 FIRE-Final Inspection1/8/20181/9/20181/9/2018 9:46:18 AMAPASS
No fire sprinklers, smoke detectors are stand-alone, fire extinguishers are mounted under kitchen sink. Final life fire safety inspection complete.
BLD15-01132 FIRE-Final Inspection1/8/20181/9/20181/9/2018 9:46:05 AMAPASS
No fire sprinklers, smoke detectors are stand-alone, fire extinguishers are mounted under kitchen sink. Final life fire safety inspection complete.
BLD16-01600 FIRE-Final Inspection1/8/20181/9/20181/9/2018 9:45:51 AMAPASS
No fire sprinklers, smoke detectors are stand-alone, fire extinguishers are mounted under kitchen sink. Final life fire safety inspection complete.
BLD16-01601 FIRE-Final Inspection1/8/20181/9/20181/9/2018 9:45:35 AMAPASS
No fire sprinklers, smoke detectors are stand-alone, fire extinguishers are mounted under kitchen sink. Final life fire safety inspection complete.
BLD16-01602 FIRE-Final Inspection1/8/20181/9/20181/9/2018 9:45:11 AMAPASS
No fire sprinklers, smoke detectors are stand-alone, fire extinguishers are mounted under kitchen sink. Final life fire safety inspection complete.
BLD17-00616 FIRE-Final Inspection1/8/20181/9/20181/9/2018 8:37:08 AMAFAIL
Replace concealed fire sprinkler escutcheons that were painted after installation. Provide fire sprinkler in data closet.