ELE13-03227
| ELE-Aging Inspection | 1/9/2019 | 1/9/2019 | 1/10/2019 2:13:58 PM | | FAIL |
|
|
permit holder making no attempt
|
ELE19-00086
| Final | 1/9/2019 | 1/9/2019 | 1/9/2019 3:56:41 PM | P | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by steve ragan...
1...riser shall be strapped within 3ft of meter 2..expansion joint shall be added to riser 3..service grounding shall be brought up to code 2 groundrods 8ft apart
4.. bonding to gas pipe shall be removed
5.. a intersystem bond bridge shall be added to grounding system
5..permit fee shall be paid to full amount required for work being done 100A branch circuit was added to detach shop and not referenced in permit fee or explanation of scope of work
|
ELE19-00105
| Electrical Rough-In | 1/9/2019 | 1/9/2019 | 1/9/2019 2:52:17 PM | P | PASS |
|
|
Please call me half an hour before inspection to insure access. Thank you Shaun ###-#### Phone #: ###-#### Inspection requested via web by Shaun Kirkman...rough ok to cover
|
ELE18-04397
| Final | 1/7/2019 | 1/9/2019 | 1/9/2019 1:39:40 PM | P | PASS |
|
|
For access please call Jaman 1/2 hr prior to inspection. ###-####. Phone #: ###-#### Inspection requested via web by Terry Scott..ok to final
|
ELE18-04098
| Final | 1/9/2019 | 1/9/2019 | 1/9/2019 1:14:57 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Therrin Robertson...ok to final
|
ELE18-04245
| Electrical Rough-In | 1/8/2019 | 1/9/2019 | 1/9/2019 11:42:48 AM | A | PASS |
|
|
Riser room walls and discuss auxiliary gutter at panel Phone #: ###-#### Inspection requested via web by Jason Parke... riser room ok to cover
|
ELE19-00094
| Electrical Rough-In | 1/9/2019 | 1/9/2019 | 1/9/2019 11:00:42 AM | A | PASS |
|
|
We cant start working here till around 9 to 930am here. rough in on the LED shoebox lights Phone #: ###-#### Inspection requested via web by Tim Dunlop.... UL listed equipment verified new LED heads for parking light poles
|
ELE19-00085
| Conference | 1/8/2019 | 1/9/2019 | 1/9/2019 10:25:42 AM | A | PASS |
|
|
Am moving a 100 AMP sub panel. Looking for the pre-start meeting. Phone #: ###-#### Inspection requested via web by Jason McKenzie moving sub panel for future addition homeowner competent...pamphlet given
|
ELE18-04585
| Rough-In Permanent Service | 1/8/2019 | 1/9/2019 | 1/9/2019 9:36:36 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Darryn Coburn... rough ok to cover light box above mst bath tub? verify fixture final p/s u/g new ok
|
ELE18-02940
| Final | 1/8/2019 | 1/9/2019 | 1/9/2019 9:21:22 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Jim Williams...ok to final
|
ELE19-00095
| Permanent Service | 1/8/2019 | 1/9/2019 | 1/8/2019 2:54:35 PM | A | PASS |
|
|
Changed out burnt up meter base Phone #: ###-#### Inspection requested via web by Kendra Lanham... p/s o/h rec ok
|
ELE18-04727
| Electrical Rough-In | 1/8/2019 | 1/9/2019 | 1/8/2019 11:42:44 AM | A | CANC |
|
|
underground, Ken Williams is contact at ###-####. Phone #: ###-#### >> Inspection requested via web by Debby Pierce Inspection cancelled from web by: Debby Pierce
|