Inspections for the day of: Thursday, January 9, 2020.
Number of inspections: 5
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE19-01403 Electrical Rough-In1/9/20201/9/20201/9/2020 2:31:14 PMPPASS
Rough inspection of boxes and raceways in elevated deck pour L3-3. Phone #: ###-#### Inspection requested via web by John Mittleider Pour noted rough in ok cover
ELE19-02136 Final1/8/20201/9/20201/9/2020 11:10:10 AMAFAIL
Final please. Have a bless day Phone #: ###-#### Inspection requested via web by Kyle Lott
At Building inspectors request need to address work done under ELE16-02769. This permit expired 5-14-19, a new permit shall be pulled covering this work and an inspection must be performed for this work. Called Kyle's number and left information with his receptionist.
110.3- Baseboard manufactureres instructions states receptacles shall not be located above baseboard heaters. 1 in down office.
210.8- GFCI receptacle devices shall be located where readily accessible. In drinking fountains.
314.29- Ceiling boxes shall be located where accessible. HVAC duct covering misc boxes rendering them not accessible.
ELE19-04512 Final1/8/20201/9/20201/9/2020 10:13:22 AMAPASS
Bill Peace is contact at ###-####. Phone #: ###-#### Inspection requested via web by Debby Pierce Final ok
ELE20-00099 Electrical Rough-In1/9/20201/9/20201/9/2020 9:37:53 AMAPASS
Install PVC from house to garage. I did tell him he could cover the middle section up but to leave the ends open to see the depth we were at a minimum of 20". He has no dogs gate is unlocked Phone #: ###-#### Inspection requested via web by David Kubik
Underground rough in ok cover
ELE20-00091 Temporary Service1/8/20201/9/20201/9/2020 8:28:57 AMAPASS
Phone #: ###-#### Inspection requested via web by Robert Murray t/s u/g n ok