BLD19-03563
| FIRE-Final Inspection | 1/8/2020 | 1/9/2020 | 1/9/2020 2:44:04 PM | P | PASS |
|
|
Fire sprinkler inspection is complete, fire alarm inspection is complete, fire extinguishers are placed with current inspection tags. Final life fire safety inspection for area of work complete.
Laren Phone #: ###-####
|
BLD19-03680
| FIRE-Final Inspection | 1/8/2020 | 1/9/2020 | 1/9/2020 2:42:42 PM | P | PASS |
|
|
No fire sprinkler modifications, no fire alarm modifications, fire extinguishers are in common areas with current inspection tags. As stated in the project description no occupancy is allowed under this permit. Final life fire safety inspection for vanilla TI complete.
Laren Phone #: ###-####
|
FIR19-00966
| INSP-Final Inspection | 1/9/2020 | 1/9/2020 | 1/9/2020 2:40:14 PM | P | PASS |
|
|
Final fire alarm inspection for area of work complete.
Contact is Dirk. Phone #: ###-#### Inspection requested via web by Morgan Ahten
|
FIR19-00601
| INSP-Sprinkler Rough-in | 1/9/2020 | 1/9/2020 | 1/9/2020 2:08:17 PM | P | FAIL |
|
|
Tenting held up by gas piping, can lights, electrical wiring and areas where the sheeting is not installed correctly, pocket between sheetrock on piping will be compromised, no cover is approved, inspection stopped on level 1.
Tenting inspection, call James when heading out Phone #: ###-#### Inspection requested via web by Anthony Minichiello
|
FIR19-00390
| INSP-Sprinkler Rough-in/Hydro | 1/8/2020 | 1/9/2020 | 1/9/2020 12:47:43 PM | A | DONE |
|
|
Hydrostatic test for overhead fire sprinkler piping witnessed, no pressure loss observed at riser provided gauges.
Phone #: ###-#### Inspection requested via web by Matthew Lewis
|
BLD19-01222
| FIRE-Final Inspection | 1/9/2020 | 1/9/2020 | 1/9/2020 12:06:44 PM | P | PASS |
|
|
Fire sprinkler inspection is complete, no fire alarm modifications, fire extinguishers are in common areas with current inspection tags. Final life fire safety inspection for area of work complete, signature card not available at time of inspection.
Zack Phone #: ###-####
|
BLD19-03698
| FIRE-Final Inspection | 1/8/2020 | 1/9/2020 | 1/9/2020 11:13:19 AM | A | FAIL |
|
|
Provide annual inspection for fire extinguisher. Install ceiling tiles that are missing, ceiling tiles must be in place or upright fire sprinkler protection will be required, a seperate permit will be required if fire sprinkler system needs modified. Provide signage at main entry reading "Door to remain unlocked while building is occupied".
John Phone #: ###-####
|
FIR19-00889
| INSP-Final Inspection | 1/9/2020 | 1/9/2020 | 1/9/2020 11:01:25 AM | P | CANC |
|
|
Contact is Dirk. Phone #: ###-#### >> Inspection requested via web by Morgan Ahten Inspection cancelled from web by: Morgan Ahten
|
FIR19-00648
| INSP-Final Inspection | 1/8/2020 | 1/9/2020 | 1/9/2020 10:42:50 AM | A | PASS |
|
|
Final fire alarm inspection for scope of work complete.
Final - Pls call Joe Taras at ###-#### or Dan Cook at ###-#### prior for access if needed. This permit was for removal of one smoke only. Thanks, Joe Phone #: ###-#### Inspection requested via web by Joe Taras
|
BLD19-01637
| FIRE-Final Inspection | 1/9/2020 | 1/9/2020 | 1/9/2020 9:43:23 AM | A | PASS |
|
|
No fire sprinkler modifications, fire alarm inspection is complete, life fire safety inspection for scope of work is complete, signatures provided on permit sign off card.
|
FIR19-00638
| INSP-Final Inspection | 1/7/2020 | 1/9/2020 | 1/9/2020 9:42:29 AM | A | PASS |
|
|
Final fire alarm inspection for scope of work is complete.
John Phone #: ###-####
|
BLD19-04986
| FIRE-Final Inspection | 1/8/2020 | 1/9/2020 | 1/9/2020 8:50:49 AM | A | PASS |
|
|
No fire sprinkler modifications, no fire alarm modifications, fire extinguishers are placed with current inspection tags. Final life fire safety inspection complete, signatures provided on permit sign off card.
Daniel Phone #: ###-####
|
FIR19-00720
| INSP-Final Inspection | 1/8/2020 | 1/9/2020 | 1/9/2020 8:35:39 AM | A | PASS |
|
|
Final fire sprinkler inspection for scope of work is complete.
RICK Phone #: ###-#### Inspection requested via web by Nathan Stenquist
|
BLD18-02545
| FIRE-Final Inspection | 1/8/2020 | 1/9/2020 | 1/9/2020 8:31:44 AM | A | FAIL |
|
|
Provide city approved drawings and small documents required for the life fire safety inspection. Addressing for corner lots needs to comply with section 505.3 of the BMC. A minimum of 18 inches of clearance from bottom of fire sprinkler head to top of storage is required per IFC and NFPA13.
Marvin Phone #: ###-####
|
FIR18-00903
| INSP-Final Inspection | 1/8/2020 | 1/9/2020 | 1/9/2020 8:27:39 AM | A | PASS |
|
|
Previously noted items have been corrected, final fire sprinkler inspection is complete.
Adam Phone #: ###-#### Inspection requested via web by Nathan Stenquist
|
BLD19-03041
| FIRE-Final Inspection | 1/9/2020 | 1/9/2020 | 1/9/2020 7:51:05 AM | A | PASS |
|
|
Fire sprinkler inspection is complete, fire alarm inspection is complete, fire extinguishers are placed with current inspection tags. Final life fire safety inspection for area of work complete, signatures provided on permit sign off card.
|
FIR19-00947
| INSP-Final Inspection | 1/6/2020 | 1/9/2020 | 1/9/2020 7:47:54 AM | A | PASS |
|
|
Final fire alarm inspection for area of work complete.
Phone #: ###-#### Inspection requested via web by jason petty
|
FIR19-00671
| INSP-Final Inspection | 1/8/2020 | 1/9/2020 | 1/9/2020 5:18:08 AM | A | CANC |
|
|
As early as possible Phone #: 2088301311 >> Inspection requested via mobile web by Nathan Price Inspection cancelled via mobile web on Thursday, January 09, 2020.
|