Inspections for the day of: Friday, October 1, 1999.
Number of inspections: 12
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Frank
TitleELE-INSPECTOR
Phone #794-1930
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE99-03283 Final10/1/199910/1/199910/11/1999 12:00:00 AMPPASS
rick--- ###-#### fn -- Final ok
ELE99-03302 Electrical Rough-In9/30/199910/1/199910/1/1999 12:00:00 AM PASS
Scheduled by a contractor via Hello! on 09/30/1999 at 11:25:02. Contact: . Final ok card signed
ELE97-04256 Final9/30/199910/1/199910/1/1999 12:00:00 AMANH
Russ Valline ###-#### (JMS - better call to see what, permit for 1997) still needs some GFCI orotection for garage recepts. 4/0 covers for boxes , box extension where boxes are not flush with combustible material
ELE99-02609 Final9/30/199910/1/199910/1/1999 12:00:00 AMAPART
barry ###-#### no final meter for p/s only
ELE99-03371 Electrical Rough-In9/30/199910/1/199910/1/1999 12:00:00 AMAPART
KF ELectric ###-#### (JMS - call when going here) walls ok & partial ceiling back half
ELE99-03504 Final9/30/199910/1/199910/1/1999 12:00:00 AMAPASS
bill ---###-#### fn ---cable from the pump to the house for well pump r/I for trench ok u/g for pump
ELE99-02451 Final9/30/199910/1/199910/1/1999 12:00:00 AMAPASS
mark ###-#### fn d (JMS) final ok card signed
ELE99-03505 Electrical Rough-In10/1/199910/1/199910/1/1999 12:00:00 AMPPASS
Scheduled by a contractor via Hello! on 10/01/1999 at 08:28:55. Contact: ###-####. Front walls & ceiling
ELE99-03140 Electrical Rough-In10/1/199910/1/199910/1/1999 12:00:00 AMPPASS
Scheduled by a contractor via Hello! on 10/01/1999 at 09:50:09. Contact: ###-####. R/s u/g new ok no r/I ok
ELE99-03139 Electrical Rough-In10/1/199910/1/199910/1/1999 12:00:00 AMPPASS
Scheduled by a contractor via Hello! on 10/01/1999 at 09:59:50. Contact: ###-####. T/s u/g new ok no r/I final ok
ELE99-03226 Permanent Service10/1/199910/1/199910/1/1999 12:00:00 AMPFAIL
ALLEN-- ###-#### PER SER notice posted nec 250-104 has water system been bonded from service? Called alan will check it out
ELE99-03014 Final9/30/199910/1/199910/1/1999 12:00:00 AMPPART
BUTCH-- ###-#### FN temp occ okay