Inspections for the day of: Tuesday, October 1, 2002.
Number of inspections: 9
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorPat Lass
TitleELE-INSPECTOR
Phone #794-9478
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE02-02251 Final9/30/200210/1/200210/1/2002 12:00:00 AMAPART
Scheduled by a contractor via Hello! on 09/30/2002 at 10:28:26. Contact: ###-####.
ELE02-02588 Electrical Rough-In9/30/200210/1/200210/1/2002 12:00:00 AMAFAIL
CALL GARY ; Phone #: ###-#### Internet Inspection Request from: Rita DeYoung
Box fill, unused openings, protection and support of romex, bond GEC raceways, working space in fornt of live parts, 6 in. of free conductor, disimilar metals and too many conductors in a lug. 10/1/2002 11:06:18 AM
ELE98-02307 Electrical Rough-In9/30/200210/1/200210/1/2002 12:00:00 AMANR
ERIC ###-####
Had conf. 10/1/2002 10:22:42 AM
ELE02-01904 Final9/30/200210/1/200210/1/2002 12:00:00 AMAPASS
###-####
ELE02-01897 Final9/30/200210/1/200210/1/2002 12:00:00 AMAPASS
ELE02-02931 Final10/1/200210/1/200210/1/2002 12:00:00 AMPPASS
###-#### bill
ELE02-02822 Final10/1/200210/1/200210/1/2002 12:00:00 AMPNH
for homeowner -ren; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie
No access 10/1/2002 3:09:03 PM
ELE02-02906 Electrical Rough-In10/1/200210/1/200210/1/2002 12:00:00 AMPPART
cole-for the house only; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie
ELE01-03949 Rough-In Permanent Service10/1/200210/1/200210/1/2002 12:00:00 AMPPASS
Scheduled by a contractor via Hello! on 10/01/2002 at 11:07:01. Contact: ###-####.
R/I to Pool equipment covered without inspection, no bonding inspection on pools
P/S U/G N Ok 10/1/2002 2:17:36 PM