ELE03-00863
| ELE-Aging Inspection | 10/1/2003 | 10/1/2003 | 10/1/2003 12:00:00 AM | | CANC |
|
|
|
ELE03-03055
| Permanent Service | 10/1/2003 | 10/1/2003 | 10/1/2003 12:00:00 AM | A | PASS |
|
|
p/s o/h new for meter
|
ELE03-03056
| Permanent Service | 10/1/2003 | 10/1/2003 | 10/1/2003 12:00:00 AM | A | PASS |
|
|
p/s o/h new for meter ok
|
ELE03-02351
| Final | 9/30/2003 | 10/1/2003 | 10/1/2003 12:00:00 AM | A | PASS |
|
|
harry; Phone #: ###-#### Internet Inspection Request from: Darla Downs ok 10/1/2003 11:09:29 AM
|
ELE03-03058
| Final | 9/30/2003 | 10/1/2003 | 10/1/2003 12:00:00 AM | A | CANC |
|
|
larry; Phone #: ###-#### Internet Inspection Request from: Darla Downs see added r/i 10/1/2003 11:09:51 AM
|
ELE03-03055
| Electrical Rough-In | 9/30/2003 | 10/1/2003 | 10/1/2003 12:00:00 AM | A | CANC |
|
|
###-#### barry see added p/s 10/1/2003 9:12:12 AM
|
ELE03-03056
| Electrical Rough-In | 9/30/2003 | 10/1/2003 | 10/1/2003 12:00:00 AM | A | CANC |
|
|
###-#### see added p/s 10/1/2003 9:13:03 AM
|
ELE03-03053
| Electrical Rough-In | 9/30/2003 | 10/1/2003 | 10/1/2003 12:00:00 AM | A | PART |
|
|
###-#### brian partial u/g ok 9/30/2003 12:53:41 PM
|
ELE02-02264
| Electrical Rough-In | 9/30/2003 | 10/1/2003 | 10/1/2003 12:00:00 AM | A | PART |
|
|
###-#### matt walls 10/1/2003 8:46:04 AM
|
ELE03-03058
| Electrical Rough-In | 10/1/2003 | 10/1/2003 | 10/1/2003 12:00:00 AM | A | PASS |
|
|
r/i ok
|
ELE03-03048
| Rough-In Permanent Service | 9/30/2003 | 10/1/2003 | 10/1/2003 12:00:00 AM | P | FAIL |
|
|
Approval for cover on the addition. New Garage will need to be inspected at a later date as we need to co-ordinate with Idaho power to move existing service. Seeking approval for cover on all walls and ceiling except the garage. ; Phone #: ###-#### Internet Inspection Request from: Joe Thomas cor. posted called 210.52(A) outlet spacing fam. rm, 300.15 needs boxes for 12/2, and 8/3 romex for future wiring, 312.5(C) exception conduit for ser cable at p/s 10/1/2003 1:18:13 PM
|
ELE03-02895
| Permanent Service | 9/30/2003 | 10/1/2003 | 10/1/2003 12:00:00 AM | P | FAIL |
|
|
christy-- ###-#### no cor posted did not have access to jbox, needs gutkit, grding all messed up needs #4 to water witin 5 ft, grd rods not 6ft apart, contractor is hunting left message with owner 10/1/2003 3:11:58 PM
|
ELE03-03065
| Rough-In Permanent Service | 10/1/2003 | 10/1/2003 | 10/1/2003 12:00:00 AM | P | NR |
|
|
###-#### ron met contractor, 210.52(A) needs outlet for wall space in kit. move outlet for washer in bathroom so it is not accessible, terminate GEC too neutral bus not equip grd bus 10/1/2003 2:33:16 PM
|