Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE02-02940 Extend Permit 180 days 10/1/200410/1/2004 12:00:00 AM PART
###-#### - dave Note: not finished yet ok 10/1/2004 7:57:46 AM
ELE04-02687 Final9/30/200410/1/200410/1/2004 12:00:00 AMAPART
john; Phone #: ###-#### Internet Inspection Request from: Barbara Moore t/o ok cor. posted called support box to structure above front door, blank 2 outlet west rest rm, remove recept from above ceiling grid for tv camera 10/1/2004 8:42:34 AM
ELE04-02920 Final9/30/200410/1/200410/1/2004 12:00:00 AMAPASS
ANDREAN; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles ok 10/1/2004 10:45:45 AM
ELE04-02166 Final9/30/200410/1/200410/1/2004 12:00:00 AMAFAIL
jon strake ###-#### 9/30/2004 4:13:01 PM cor. posted met contractor needs to bond to sprinkler system ,use GE brackers only, 410.14 hole in fixture too access box, use manufactures boxes and fittings for plugmold, to maintain electrical and mechanical continuity from box to plugmold, use makers listed neutral bus at p/s 10/1/2004 9:56:38 AM
ELE04-03013 Temporary Service10/1/200410/1/200410/1/2004 12:00:00 AMPPASS
###-#### tarrin t/s u/g new ok 10/1/2004 12:54:50 PM
ELE04-01075 Final10/1/200410/1/200410/1/2004 12:00:00 AMPFAIL
VERNA; Phone #: ###-#### Internet Inspection Request from: Barbara Moore cor. posted called left message 110.26(F)(2) remove pipes from below p/s, 410.8 clearence MB closet fixtures both units 210.52(A) needs outlet foe fixed panel sliders both units 210.8 gfci all outlets kit 10/1/2004 1:39:30 PM
ELE04-03007 Electrical Rough-In10/1/200410/1/200410/1/2004 12:00:00 AMPFAIL
gary; Phone #: ###-#### Internet Inspection Request from: Barbara Moore cor. posted called countertop outlet spacing needs 1 for appliance garage, 4ft spacing at pass through counter kit. and din rm,make sure all splices are made up tight and use approved crimp tool nail plates and 1 1/4" , staple cables within 8 " of boxes 10/1/2004 3:37:15 PM
ELE04-03015 Electrical Rough-In10/1/200410/1/200410/1/2004 12:00:00 AMPPART
pool bonnd inspection please////###-#### emmett bond and pvc from light shell ok partial only there will be more bonding and u/g 10/1/2004 2:55:49 PM
ELE04-03018 Permanent Service10/1/200410/1/200410/1/2004 12:00:00 AMPFAIL
###-#### - brett
cor. posted called needs types fuses and adapters to protect wires at proper amps , install 2 grd rods 10/1/2004 4:16:47 PM