Inspections for the day of: Friday, October 1, 2004.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD03-01324 FIRE-Final Inspection9/28/200410/1/200410/1/2004 12:00:00 AMACANC
duplicate inspection 10/1/2004 11:15:44 AM
FIR04-00521 INSP-Final Inspection9/30/200410/1/200410/1/2004 12:00:00 AMAFAIL
Provide revised sway bracing calcs to bill alexander. Forward flush passed. Hydro test failed. Rescheduled for this afternoon 10/1/2004 11:34:00 AM
BLD04-01476 FIRE-Final Inspection9/30/200410/1/200410/1/2004 12:00:00 AMAFAIL
Provide annual inspection for the fire extinguisher. See review note #2. Install door hardware so compliance can be verified. See review note #4. Provide verification to inspector that cfm rating for hvac unit. See note #17 for hvac shutdown requirements. Test emergency lights for inspector. 10/1/2004 8:51:38 AM
BLD03-01324 FIRE-Final Inspection10/1/200410/1/200410/1/2004 12:00:00 AMAPASS
Fire life safety finaled
FIR04-00227 INSP-Final Inspection10/1/200410/1/200410/1/2004 12:00:00 AMPPASS
Fire sprinkler permit finaled 9/1/2004 3:10:06 PM
FIR04-00368 INSP-Sprinkler Rough-in10/1/200410/1/200410/1/2004 12:00:00 AMPPASS
second and third floor sprinkler piping is ok to cover. Contractor still needs to provide engineering ok for support of piping on the bottom chords. I notified eric with treasure valley fire that piping will need to go to top chord and all ceilings removed if verification is not provided. 9/1/2004 3:52:17 PM
FIR04-00521 INSP-Sprinkler Rough-in/Hydro10/1/200410/1/200410/1/2004 12:00:00 AMPPASS
hydro test passed. Need test papers 9/1/2004 3:02:45 PM
FIR04-00550 INSP-Final Inspection10/1/200410/1/200410/1/2004 12:00:00 AMPCANC
Per Troy Nelson to be rescheduled for next week. 9/1/2004 4:54:58 PM
FIR04-00478 INSP-Final Inspection9/30/200410/1/200410/1/2004 12:00:00 AMPFAIL
Room 317 no longer exists, its now a therapy room. Change description on fire alarm panel.
Provide a visual device in the short corridor on the south side of the nurses station 9/1/2004 3:15:59 PM
FIR04-00478 INSP-Alarm Testing9/30/200410/1/20049/30/2004 12:00:00 AMPDONE
thad; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles