Inspections for the day of: Monday, October 1, 2007.
Number of inspections: 12
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR07-00247 FIR-Aging Inspection10/1/200710/1/200710/3/2007 11:36:08 AM DEFR
FIR07-00797 INSP-Final Inspection10/1/200710/1/200710/1/2007 4:10:50 PMPPASS
Fire sprinkler work passed, permit finaled.
FIR07-00425 INSP-Sprinkler Rough-in10/1/200710/1/200710/1/2007 3:58:48 PMPPART
First and second floors are okay for cover as noted, one DSW at each level is not installed, one head to be added at the 1st floor, also discussed roof hose connection.
FIR07-00681 INSP-Sprinkler Rough-in9/28/200710/1/200710/1/2007 2:38:32 PMPPART
Fire sprinkler modifications at the drop ceilings are okay for cover, noted three heads not yet complete at hard lid areas, upright coverage for the mezz. storage area is not shown on plans or installed at this time, need to provide area separation as discussed with the general contractor.
FIR07-00623 INSP-Final Inspection10/1/200710/1/200710/1/2007 2:34:07 PMPPASS
Fire sprinkler permit finaled.
BLD07-00494 FIRE-Final Inspection10/1/200710/1/200710/1/2007 2:33:16 PMPFAIL
Need project related fire alarm and hood suppression system permits finaled prior to life safety approval.
BLD06-02555 FIRE-Final Inspection10/1/200710/1/200710/1/2007 2:31:42 PMPPASS
Fire life safety is satisfactory, noted two fire extinguishers on site to be installed per review notes and plan annotations sheet A2.2, can be verified at structural final.
FIR07-00554 INSP-Final Inspection10/1/200710/1/200710/1/2007 2:28:02 PMPPASS
Fire sprinkler work passed final inspection, permit finaled.
BLD07-00494 FIRE-Final Inspection9/28/200710/1/200710/1/2007 11:20:09 AMACANC
###-#### - mike Note: hood final Not ready for inspection per phone call from contractor due to electrical issues.
FIR07-00737 INSP-Conference10/1/200710/1/200710/1/2007 11:14:22 AMADONE
On site conference to discuss project shell and tenant work interface, also discussed second floor ceilings.
FIR07-00729 INSP-Sprinkler Rough-in/Hydro10/1/200710/1/200710/1/2007 11:11:26 AMAPART
Fire sprinkler system modifications are approved for cover at the drop ceilings.
FIR07-00661 INSP-Sprinkler Rough-in/Hydro10/1/200710/1/200710/1/2007 11:10:04 AMAPART
Overhead install is acceptable, need as-built plans showing field modifications at the escalator.