FIR08-00553
| INSP-Final Inspection | 10/1/2008 | 10/1/2008 | 10/1/2008 4:55:04 PM | P | FAIL |
|
|
Noted overspaced smoke detection, one detector to be relocated due to proximity to HVAC diffuser, need to relocate SD at the FACP, missing signage at the door to the control panel room, no testing completed at this time, see plans for annotations.
|
FIR08-00433
| INSP-Sprinkler Rough-in/Hydro | 10/1/2008 | 10/1/2008 | 10/1/2008 3:49:32 PM | P | PASS |
|
|
Underground hydro completed. KR
|
FIR08-00278
| INSP-Final Inspection | 9/30/2008 | 10/1/2008 | 10/1/2008 2:27:55 PM | A | PART |
|
|
Fire alarm system testing passed however central station did not report signals recieved for three duct detectors and two smoke detectors at the fire door.
|
FIR08-00289
| INSP-Final Inspection | 9/30/2008 | 10/1/2008 | 10/1/2008 2:26:02 PM | A | FAIL |
|
|
Need to provide a PRV at the riser due to the grid system design, noted one leaking sprinkler drop above the restroom ceiling, forward flow testing of the DC backflow preventer failed.
|
FIR08-00424
| INSP-Final Inspection | 9/30/2008 | 10/1/2008 | 10/1/2008 2:23:28 PM | A | NR |
|
|
Work is not complete for inspection at this time. The spray booth has not been installed.
|
BLD07-03163
| FIRE-Final Inspection | 9/30/2008 | 10/1/2008 | 10/1/2008 2:19:41 PM | A | NR |
|
|
Need project related fire alarm and sprinkler permit finals prior to building life safety approvals.
|
BLD07-03241
| FIRE-Final Inspection | 9/30/2008 | 10/1/2008 | 10/1/2008 2:18:34 PM | A | PASS |
|
|
Fire life safety inspection completed acceptable, noted blocked exit path at the 2nd floor stairway north side to be cleared prior to structural final.
|
BLD08-00848
| FIRE-Final Inspection | 9/30/2008 | 10/1/2008 | 10/1/2008 2:12:54 PM | A | FAIL |
|
|
Need to provide approved hardware at the press box exit door, missing lane marking per plans adjacent to the emergency vehicle access gate, see fire code review notes for details.
|