Inspections for the day of: Wednesday, October 1, 2008.
Number of inspections: 8
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR08-00626 INSP-Sprinkler Rough-in10/1/200810/1/200810/1/2008 4:14:35 PMPPASS
The remaining underground piping is ok to cover.
BLD07-03079 FIRE-Final Inspection9/29/200810/1/200810/1/2008 4:07:33 PMPFAIL
Life safety will be ok to pass when the fire alarm permit is finaled
FIR08-00533 INSP-Final Inspection9/29/200810/1/200810/1/2008 4:05:22 PMPCANC
Neither flow switch would activate the outside alarm bell.
BLD07-03031 FIRE-Final Inspection9/29/200810/1/200810/1/2008 3:54:14 PMPPASS
life safety paased
FIR08-00534 INSP-Final Inspection9/29/200810/1/200810/1/2008 3:53:39 PMPPASS
Permit finaled
FIR08-00331 INSP-Sprinkler Rough-in/Hydro10/1/200810/1/200810/1/2008 3:09:00 PMPPASS
The underground hydro test passed.
BLD08-01917 FIRE-Final Inspection10/1/200810/1/200810/1/2008 2:18:18 PMPFAIL
Repair the exit sign and reverse the door hardware as marked on the city approved plans.
FIR08-00299 INSP-Sprinkler Rough-in9/30/200810/1/200810/1/2008 10:32:54 AMADONE
Start of the 24 hour air test with 41.5 psi on the left system riser and 43 psi on the right system riser.