Inspections for the day of: Monday, October 1, 2012.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR12-00494 INSP-Sprinkler Rough-in10/1/201210/1/201210/1/2012 3:46:06 PMPPASS
See the city approved plans for the location where sprinkler piping can be covered which has been clouded in red and given todays date. Also see adjacent location where three corrections will be required prior to a cover approval being given.
BLD12-02590 FIRE-Final Inspection10/1/201210/1/201210/1/2012 3:28:25 PMPFAIL
Annual inspection for the fire extinguisher is needed.
FIR12-00538 INSP-Sprinkler Rough-in10/1/201210/1/201210/1/2012 3:21:00 PMPPASS
Sprinkler piping above the hardlids in this scope of work is ok to cover.
FIR12-00556 INSP-Sprinkler Rough-in10/1/201210/1/201210/1/2012 2:08:41 PMPPASS
Sprinkler piping within the scope of work can be covered.
FIR12-00395 INSP-Sprinkler Rough-in9/28/201210/1/201210/1/2012 1:39:14 PMAFAIL
Third floor tenting has not been repaired or completed. Piping can not be covered.
FIR12-00417 INSP-Sprinkler Rough-in9/28/201210/1/201210/1/2012 1:38:18 PMAPART
First and second floor sprinkler rough-in passed. One pendant was missing on the second floor but can be verified at the next rough-in inspection. Third floor hydraulic calculations need to be re-verified due to pipe routing changes in the remote area. Also tenting has not been done for the third floor or any of the heat trace tape. First and second floor piping can be covered except for the areas where heat trace will need to be inspected.
BLD12-02370 FIRE-Final Inspection9/28/201210/1/201210/1/2012 9:33:47 AMAPASS
Life safety passed
BLD12-01441 FIRE-Final Inspection9/28/201210/1/201210/1/2012 9:33:20 AMAPASS
Life safety passed
FIR12-00231 FIR-Aging Inspection10/1/201210/1/201210/1/2012 8:13:51 AM NR
Per Mary, she is waiting for a call back from Albertsons and then will schedule the inspection.
FIR12-00490 INSP-Sprinkler Rough-in/Hydro9/28/201210/1/201210/1/2012 8:00:21 AMACANC
Need an Underground Hydro inspection 1st thing in the morning if possible - Brian Dunham is the contact at 570.0497 Phone #: ###-#### >> Inspection requested via web by Kindel de Leon Inspection cancelled from web by: Scott Carter II