Inspections for the day of: Tuesday, October 1, 2013.
Number of inspections: 8
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD11-00907 FIRE-Final Inspection10/1/201310/1/201310/2/2013 10:39:17 AMPPASS
Fire life safety inspection passed. *Note- no signature card available on site*
FIR13-00397 INSP-Final Inspection9/30/201310/1/201310/1/2013 4:40:27 PMPPASS
Previous correction items finished. Reinspection passed. Fire alarm permit finaled.
FIR13-00170 INSP-Final Inspection9/30/201310/1/201310/1/2013 3:22:41 PMAPART
Completed fire alarm testing for buildings 8, 9, 10, and 11. Also finished reinspection for previous correction items at building 4. Correction and adjustment items noted today include; non-functional visual notification at ADA unit 1013, plans show incorrect room numbers for FACP units in buildings 6 and 9, MP stations for panel at buildings 5,6, and 7 did not activate horn strobes.
FIR13-00305 INSP-Final Inspection9/30/201310/1/201310/1/2013 1:07:26 PMAPART
Completed walkthrough- Need to install missing heads at the garage/riser areas, secure control valves at the riser, include finish pack with spare heads, calc sticker, etc. Flow switch tested okay, one missing escutcheon installed while on site. Need to provide thermal barrier or meet conditions for exposed CPVC pipe at the ground level unfinished bedroom, family room, WIC and under stair storage areas.
FIR13-00387 INSP-Final Inspection9/30/201310/1/201310/1/2013 1:02:16 PMAPASS
Previous correction item verified for completion. Final walkthrough passed. Fire sprinkler permit finaled.
BLD13-02149 FIRE-Final Inspection9/30/201310/1/201310/1/2013 1:00:50 PMAPASS
Fire life safety inspection completed acceptable.
FIR13-00527 INSP-Final Inspection9/30/201310/1/201310/1/2013 12:59:54 PMAPASS
Fire sprinkler work passed both rough-in and final inspections. Permit finaled.
BLD13-02382 FIRE-Final Inspection9/30/201310/1/201310/1/2013 12:57:31 PMAPASS
Life safety inspection completed satisfactory. PFE at the mezzanine level to be installed on a bracket as discussed.