BLD13-02474
| FIRE-Final Inspection | 9/30/2013 | 10/1/2013 | 10/2/2013 8:28:04 AM | A | PART |
|
|
A temporary occupancy was already given by Craig. Provide emergency lighting as shown on the plans and discussed. Provide exit sign as shown on the plans. Repair the exit sign at the main exit. Provide address.
|
FIR13-00453
| INSP-Sprinkler Rough-in | 10/1/2013 | 10/1/2013 | 10/1/2013 3:42:51 PM | P | PART |
|
|
The underground supply line from the street to the first fitting is ok to cover.
|
FIR13-00286
| INSP-Sprinkler Rough-in | 10/1/2013 | 10/1/2013 | 10/1/2013 3:29:20 PM | P | PASS |
|
|
See the city approved plans for locations where the sprinkler piping can be covered.
|
BLD12-03337
| FIRE-Conference | 10/1/2013 | 10/1/2013 | 10/1/2013 3:22:10 PM | P | DONE |
|
|
Went over life safety requirements with Lilly.
|
FIR13-00113
| INSP-Final Inspection | 9/30/2013 | 10/1/2013 | 10/1/2013 2:50:11 PM | P | PASS |
|
|
Permit finaled
|
FIR13-00442
| INSP-Alarm Testing | 9/25/2013 | 10/1/2013 | 10/1/2013 2:49:28 PM | A | CANC |
|
|
8am -- Alex Phone #: ###-####
|
FIR13-00488
| INSP-Sprinkler Rough-in | 9/30/2013 | 10/1/2013 | 10/1/2013 2:40:26 PM | A | PART |
|
|
Sprinkler piping is ok to cover but many of the pendants need to be relocated 6"away from the 4" soffit to meet nfpa 13. They will be checkeed at the final inspection per our conversation.
|
BLD11-02973
| FIRE-Final Inspection | 9/30/2013 | 10/1/2013 | 10/1/2013 9:39:04 AM | A | PASS |
|
|
life safety passed
|