Inspections for the day of: Thursday, October 1, 2015.
Number of inspections: 3
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorThomas Walsh
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR14-00598 INSP-Sprinkler Rough-in9/30/201510/1/201510/1/2015 1:41:18 PMPPASS
Rough to cover inspection for EFG parking garage wet pipe system. System has already been hydrotested.
PASSED - OK to cover all pipe for this system.
FIR14-00778 INSP-Sprinkler Rough-in/Hydro9/30/201510/1/201510/1/2015 1:39:33 PMPPART
Bldg EFG dry pipe system air test (start)
42 psi @ 1300 hrs.
FIR14-00850 INSP-Alarm Testing10/1/201510/1/201510/1/2015 12:27:29 PMAPASS
Test of newly added antenna to improve communication of system alarms to monitoring station. This was required due to impact of the metal security screen installed along the entire perimeter of the parking garage, that affected the cellular dialer from transporting alarm signals off-site to the monitoring station.