FIR14-00598
| INSP-Sprinkler Rough-in | 9/30/2015 | 10/1/2015 | 10/1/2015 1:41:18 PM | P | PASS |
|
|
Rough to cover inspection for EFG parking garage wet pipe system. System has already been hydrotested. PASSED - OK to cover all pipe for this system.
|
FIR14-00778
| INSP-Sprinkler Rough-in/Hydro | 9/30/2015 | 10/1/2015 | 10/1/2015 1:39:33 PM | P | PART |
|
|
Bldg EFG dry pipe system air test (start) 42 psi @ 1300 hrs.
|
FIR14-00850
| INSP-Alarm Testing | 10/1/2015 | 10/1/2015 | 10/1/2015 12:27:29 PM | A | PASS |
|
|
Test of newly added antenna to improve communication of system alarms to monitoring station. This was required due to impact of the metal security screen installed along the entire perimeter of the parking garage, that affected the cellular dialer from transporting alarm signals off-site to the monitoring station.
|