Inspections for the day of: Monday, October 1, 2018.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE18-03740 Conference9/30/201810/1/201810/1/2018 2:46:27 PMPPASS
Duke is your contact - conference on electrical and direction Phone #: ###-#### Inspection requested via web by Matthew White
Contractor hired to investigate electrical of residence. Verify grounding electrode system, ground rod has 26" not driven, should correct.
All grounding type receptacle outlets installed on ungrounded circuits to be GFCI protected or changed to 2 wire receptacles.
Garage furnace has exposed conductors feeding it, will remove branch circuit and replace correctly if requested.
Will remove any flexible cords running in or on or through walls and ceilings.
A large garage area has many areas with expose old cloth type ungrounded wiring and NM cable run through walls and ceilings. Many conduit runs without being properly supported and secured.
Looks like previous owners have installed a lot of wiring without permitting or inspections.
Contractor to be very specific with documenting work performed.
ELE18-02233 Final9/14/201810/1/201810/1/2018 1:41:08 PMPDONE
Check if hot tub installed in violation of NEC and permitting. Job finaled.
Unable to verify without trespassing on some properties. As of final date hot tub had not been installed.
ELE18-03607 Electrical Rough-In10/1/201810/1/201810/1/2018 1:20:44 PMPFAIL
For North canopy Phone #: ###-#### Inspection requested via web by Ron Zimmerman
330.30- MC cables shall be secured with in 12" of each box. All are 3' to 4' support to box.
ELE18-03754 Electrical Rough-In10/1/201810/1/201810/1/2018 1:07:47 PMPPASS
Phone #: ###-#### Inspection requested via web by Brad Girard
Wall rough in ok cover
ELE18-03320 Electrical Rough-In10/1/201810/1/201810/1/2018 12:14:36 PMAPASS
Phone #: ###-#### Inspection requested via web by Kerri Hamilton
North and west and interior except panel wall rough in ok cover
ELE18-02181 Electrical Rough-In9/28/201810/1/201810/1/2018 11:17:54 AMAPASS
Electrical Underground Rough-In Phone #: ###-#### Inspection requested via web by Bryan Atkins
Underground 2- 1" from building to gate rough in ok cover
ELE18-03221 Final9/30/201810/1/201810/1/2018 11:02:20 AMAPASS
Phone #: ###-#### Inspection requested via web by Kyle Dillon
No dishwasher set electrical safe.
Final ok
ELE18-03669 Permanent Service9/24/201810/1/201810/1/2018 10:43:42 AMAFAIL
Perm Service Inspection for replacing Main Breaker. Any questions please call Jordan At ###-#### Phone #: ###-#### Inspection requested via web by Louis Keller
250.24- Main bonding jumper shall be installed to connect panel can to grounding and grounded conductors,
250.53(A)(2)- Metal underground water pipe grounding electrode system shall be supplemented by an additional ground rod.
250.66- Grounding electrode conductor splice shall be of minimum size to grounded conductor connection.
ELE18-03148 Final9/28/201810/1/201810/1/2018 10:02:29 AMAPASS
Electrical final for men and womens bathroom. Esi super should be on site for inspection. If not call with questions. Phone #: ###-#### Inspection requested via web by Garrett Collins Final ok
ELE18-02815 Final9/30/201810/1/201810/1/2018 9:44:08 AMAPASS
Cameron will in lock the door for you Phone #: ###-#### Inspection requested via web by Neal Rumsey Final ok
ELE18-03675 Rough-In Permanent Service9/28/201810/1/201810/1/2018 9:24:13 AMAPASS
Phone #: ###-#### Inspection requested via web by Heath Thomas
Paddle fan boxes in all bedrooms and living rm. Rough in ok cover p/s u/g n ok