ELE18-03740
| Conference | 9/30/2018 | 10/1/2018 | 10/1/2018 2:46:27 PM | P | PASS |
|
|
Duke is your contact - conference on electrical and direction Phone #: ###-#### Inspection requested via web by Matthew White Contractor hired to investigate electrical of residence. Verify grounding electrode system, ground rod has 26" not driven, should correct. All grounding type receptacle outlets installed on ungrounded circuits to be GFCI protected or changed to 2 wire receptacles. Garage furnace has exposed conductors feeding it, will remove branch circuit and replace correctly if requested. Will remove any flexible cords running in or on or through walls and ceilings. A large garage area has many areas with expose old cloth type ungrounded wiring and NM cable run through walls and ceilings. Many conduit runs without being properly supported and secured. Looks like previous owners have installed a lot of wiring without permitting or inspections. Contractor to be very specific with documenting work performed.
|
ELE18-02233
| Final | 9/14/2018 | 10/1/2018 | 10/1/2018 1:41:08 PM | P | DONE |
|
|
Check if hot tub installed in violation of NEC and permitting. Job finaled. Unable to verify without trespassing on some properties. As of final date hot tub had not been installed.
|
ELE18-03607
| Electrical Rough-In | 10/1/2018 | 10/1/2018 | 10/1/2018 1:20:44 PM | P | FAIL |
|
|
For North canopy Phone #: ###-#### Inspection requested via web by Ron Zimmerman 330.30- MC cables shall be secured with in 12" of each box. All are 3' to 4' support to box.
|
ELE18-03754
| Electrical Rough-In | 10/1/2018 | 10/1/2018 | 10/1/2018 1:07:47 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Brad Girard Wall rough in ok cover
|
ELE18-03320
| Electrical Rough-In | 10/1/2018 | 10/1/2018 | 10/1/2018 12:14:36 PM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Kerri Hamilton North and west and interior except panel wall rough in ok cover
|
ELE18-02181
| Electrical Rough-In | 9/28/2018 | 10/1/2018 | 10/1/2018 11:17:54 AM | A | PASS |
|
|
Electrical Underground Rough-In Phone #: ###-#### Inspection requested via web by Bryan Atkins Underground 2- 1" from building to gate rough in ok cover
|
ELE18-03221
| Final | 9/30/2018 | 10/1/2018 | 10/1/2018 11:02:20 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Kyle Dillon No dishwasher set electrical safe. Final ok
|
ELE18-03669
| Permanent Service | 9/24/2018 | 10/1/2018 | 10/1/2018 10:43:42 AM | A | FAIL |
|
|
Perm Service Inspection for replacing Main Breaker. Any questions please call Jordan At ###-#### Phone #: ###-#### Inspection requested via web by Louis Keller 250.24- Main bonding jumper shall be installed to connect panel can to grounding and grounded conductors, 250.53(A)(2)- Metal underground water pipe grounding electrode system shall be supplemented by an additional ground rod. 250.66- Grounding electrode conductor splice shall be of minimum size to grounded conductor connection.
|
ELE18-03148
| Final | 9/28/2018 | 10/1/2018 | 10/1/2018 10:02:29 AM | A | PASS |
|
|
Electrical final for men and womens bathroom. Esi super should be on site for inspection. If not call with questions. Phone #: ###-#### Inspection requested via web by Garrett Collins Final ok
|
ELE18-02815
| Final | 9/30/2018 | 10/1/2018 | 10/1/2018 9:44:08 AM | A | PASS |
|
|
Cameron will in lock the door for you Phone #: ###-#### Inspection requested via web by Neal Rumsey Final ok
|
ELE18-03675
| Rough-In Permanent Service | 9/28/2018 | 10/1/2018 | 10/1/2018 9:24:13 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Heath Thomas Paddle fan boxes in all bedrooms and living rm. Rough in ok cover p/s u/g n ok
|