Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
MEC18-04023 Rough-in9/28/201810/1/201810/1/2018 11:40:51 AMAFAIL
Phone #: ###-#### Inspection requested via web by Amanda Farnsworth
Framing for fire/smoke damper does not meet manufacturer installations. 1 1/2" max space from framing to duct. Correction is for rtu 7 shaft