MEC19-03019
| Final | 10/1/2019 | 10/1/2019 | 10/1/2019 3:54:35 PM | P | PASS |
|
|
vinnie ###-#### Phone #: ###-#### Inspection requested via web by Mike Almanza- fireplace final ok
|
MEC19-04239
| Final | 9/24/2019 | 10/1/2019 | 10/1/2019 3:51:09 PM | P | PASS |
|
|
INSTALLER JAROD ###-#### Phone #: ###-#### Inspection requested via web by Aaron Alandt- furnace a/c coil co ok- 5lb flue test pass
|
MEC19-04197
| Final | 9/27/2019 | 10/1/2019 | 10/1/2019 3:24:25 PM | P | PASS |
|
|
Contact Robert (QHC) @ ###-#### or QHC Office @ Phone #: ###-#### Inspection requested via web by Kevin Pratley- 2 tube heater and gas piping final ok
|
MEC19-04264
| Final | 9/25/2019 | 10/1/2019 | 10/1/2019 2:52:06 PM | P | PASS |
|
|
Please call Dave to ensure install is complete. Thank you! ###-#### Phone #: ###-#### Inspection requested via web by Rick Borg- furnace a/c coil co ok
|
MEC19-03412
| Final | 10/1/2019 | 10/1/2019 | 10/1/2019 2:24:06 PM | P | PASS |
|
|
bath fan light combo ok
|
MEC19-03258
| Final | 10/1/2019 | 10/1/2019 | 10/1/2019 2:23:09 PM | P | PASS |
|
|
Customer Contact: Michelle ###-#### HVAC Contact: Jeremy ###-#### Phone #: ###-#### Inspection requested via web by Arielle Hendricks- 2 head mini split ok in garage
|
MEC19-04137
| Rough-in | 10/1/2019 | 10/1/2019 | 10/1/2019 1:59:03 PM | P | PART |
|
|
Dryer vent inspection Phone #: ###-#### Inspection requested via web by RaChelle Frisbee- dryer duct in wall ok to cover- will look at roof penetration and duct above ceiling on next R/I inspection
|
MEC19-04246
| Conference | 10/1/2019 | 10/1/2019 | 10/1/2019 1:36:25 PM | P | PASS |
|
|
Phone #: 2088718789 >> Inspection requested via mobile web by Albert- light test hood connection ok- ok for firewrap
|
MEC19-04246
| Pressure Test | 10/1/2019 | 10/1/2019 | 10/1/2019 1:35:54 PM | P | PASS |
|
|
Phone #: 2088718789 >> Inspection requested via mobile web by Albert- 60lb gas pass
|
MEC17-03568
| Final | 10/1/2019 | 10/1/2019 | 10/1/2019 12:54:56 PM | P | PASS |
|
|
Barbara Phone #: ###-####- gas piping and fireplace were omitted on this job- R/I ok
|
MEC17-03568
| Final | 10/1/2019 | 10/1/2019 | 10/1/2019 12:54:26 PM | P | PASS |
|
|
Barbara Phone #: ###-####- final ok- gas piping was omitted on this job-
|
MEC19-03400
| Conference | 10/1/2019 | 10/1/2019 | 10/1/2019 12:29:42 PM | P | PASS |
|
|
12-1 Duct Blast Inspection requested via web by Konrad Swartz- duct blast test pass
|
MEC19-03399
| Conference | 10/1/2019 | 10/1/2019 | 10/1/2019 12:29:12 PM | P | PASS |
|
|
duct blast test pass
|
MEC19-03398
| Conference | 10/1/2019 | 10/1/2019 | 10/1/2019 12:28:06 PM | P | CANC |
|
|
12-1 Duct Blast Inspection requested via web by Konrad Swartz- wrong address for duct blast
|
MEC19-03985
| Pressure Test | 9/30/2019 | 10/1/2019 | 10/1/2019 12:00:41 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Gary Reeves- 20lb gas pass- tagged meter location
|
MEC19-03985
| Rough-in | 10/1/2019 | 10/1/2019 | 10/1/2019 12:00:20 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Gary Reeves- R/I ok
|
MEC19-04326
| Rough-in | 10/1/2019 | 10/1/2019 | 10/1/2019 11:36:40 AM | P | CANC |
|
|
Phone #: ###-#### Inspection requested via web by Oleg Chervak- wont be ready y time i come back by- reschedule
|
MEC19-04327
| Rough-in | 10/1/2019 | 10/1/2019 | 10/1/2019 11:36:15 AM | P | CANC |
|
|
Phone #: ###-#### Inspection requested via web by Oleg Chervak- wont be ready by time i come back by- reschedule
|
MEC19-04326
| Pressure Test | 10/1/2019 | 10/1/2019 | 10/1/2019 11:35:48 AM | P | CANC |
|
|
Phone #: ###-#### Inspection requested via web by Oleg Chervak- already completed
|
MEC19-04326
| Rough-in | 9/30/2019 | 10/1/2019 | 10/1/2019 11:35:27 AM | A | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by Oleg Chervak- 1- need ladder provided by contractor to access furnace in attic 2- framing needs completed around b vent 2nd floor and draftstop installled 3- exhaust fan 2nd floor shall terminate 4 feet from property line 4- need to insulate bare metal in att supply and r/a 5- need to seal dryer duct to termination box 6- need 6" fresh air installed and maintain 10 feet from exhaust ducts 7- flue shall be b vent off furnace remove single wall pipe/fitting left notice
|
MEC19-04326
| Pressure Test | 9/30/2019 | 10/1/2019 | 10/1/2019 11:32:20 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Oleg Chervak- 20lb gas pass tagged meter location
|
MEC19-04327
| Rough-in | 9/30/2019 | 10/1/2019 | 10/1/2019 11:20:53 AM | A | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by Oleg Chervak- 1- framing needs completed around b vent 2nd floor and draftstop installed correctly 2- dryer duct to termination box needs sealed 3- need 6" fresh air ran and maintain 10 feet from exhaust 4- exhaust fan shall terminate 4 feet from property line 2nd flood 5 need all bare metal in attic insulated off furnace supply and R/A
|
MEC19-04327
| Pressure Test | 9/30/2019 | 10/1/2019 | 10/1/2019 11:16:18 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Oleg Chervak- 20lb gas pass- tagged meter location
|
MEC19-04312
| Final | 9/30/2019 | 10/1/2019 | 10/1/2019 11:05:12 AM | P | PASS |
|
|
Please call Craig on your way - ###-#### Phone #: ###-#### Inspection requested via web by Arielle Hendricks- a/c coil co ok
|
MEC19-04321
| Final | 9/30/2019 | 10/1/2019 | 10/1/2019 10:35:33 AM | A | FAIL |
|
|
THIS INSPECTION IS FOR ROUGHIN/FINAL , PLEASE CALL GLEN WITH ANY QUESTIONS Phone #: ###-#### Inspection requested via web by Yvonne Bowman- need to add wet switch to 3 secondarys at coil location- need uv protection outside at lineset and seal all lineset penetrations weather tight- need to check valuation since 3 furnaces coils and a/cs were installed not RTU as listed
|
MEC19-04159
| Rough-in | 9/28/2019 | 10/1/2019 | 10/1/2019 10:17:28 AM | A | FAIL |
|
|
Call 1/2 hour prior for homeowner to meet you at the home. Thanks Phone #: ###-#### Inspection requested via web by Rene Neumeyer- draft stop needs framed in exterior wall- need gas shut off accessable at fireplace is dante valve being used ??
|
MEC19-04331
| Rough-in | 9/30/2019 | 10/1/2019 | 10/1/2019 9:38:43 AM | A | PASS |
|
|
PHYLLIS ###-#### Phone #: ###-#### Inspection requested via web by Mike Almanza- R/I ok
|
MEC19-04331
| Final | 10/1/2019 | 10/1/2019 | 10/1/2019 9:38:26 AM | A | PASS |
|
|
PHYLLIS ###-#### Phone #: ###-#### Inspection requested via web by Mike Almanza- fireplace final ok
|
MEC19-04331
| Pressure Test | 9/30/2019 | 10/1/2019 | 10/1/2019 9:38:01 AM | A | PASS |
|
|
PHYLLIS ###-#### Phone #: ###-#### Inspection requested via web by Mike Almanza- 20lb gas pass- need to firecaulk gas penetration inside garage at furnace location thru floor
|
MEC19-04319
| Final | 10/1/2019 | 10/1/2019 | 10/1/2019 9:22:05 AM | A | PASS |
|
|
Inspection requested via web by Floyd Floyd Peek- insulation flex and registers ok- final ok- card signed
|
MEC19-04137
| Rough-in | 9/30/2019 | 10/1/2019 | 10/1/2019 9:04:26 AM | A | CANC |
|
|
Dryer vent inspection Phone #: ###-#### Inspection requested via web by RaChelle Frisbee- no dryer duct installed- talked with contractor- will reschedule
|
MEC19-03443
| Final | 9/27/2019 | 10/1/2019 | 10/1/2019 8:47:27 AM | A | CANC |
|
|
JOB CONTACT - AB ###-#### Phone #: ###-#### Inspection requested via web by BECCA DUMMER- bld under review- need plan mod excepted and new approved prints from plan mod onsite for inspection
|
MEC19-03450
| Final | 9/30/2019 | 10/1/2019 | 10/1/2019 8:26:28 AM | A | PASS |
|
|
David is homeowner (number provided). Please give him a heads up when you are on your way to ensure he is home. He should be there, though. If you run into any issues, please call Alyssa at ###-####. Phone #: ###-#### Inspection requested via web by Alyssa Cromwell- final ok
|
MEC19-03404
| Conference | 9/30/2019 | 10/1/2019 | 10/1/2019 8:04:18 AM | P | CANC |
|
|
12-1 Duct Blast Air Balance on 2 units >> Inspection requested via web by Konrad Swartz Inspection cancelled from web by: Konrad Swartz
|
MEC19-00907
| Mec-Aging Inspection | 10/1/2019 | 10/1/2019 | 10/1/2019 7:51:53 AM | | FAIL |
|
|
contractor needs to schedule inspection if works complete- permit will expire next aging if no activity
|