Inspections for the day of: Tuesday, October 1, 2019.
Number of inspections: 35
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBrian Scoles
TitleMEC INSPECTOR
Phone #914-4915
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
MEC19-03019 Final10/1/201910/1/201910/1/2019 3:54:35 PMPPASS
vinnie ###-#### Phone #: ###-#### Inspection requested via web by Mike Almanza- fireplace final ok
MEC19-04239 Final9/24/201910/1/201910/1/2019 3:51:09 PMPPASS
INSTALLER JAROD ###-#### Phone #: ###-#### Inspection requested via web by Aaron Alandt- furnace a/c coil co ok- 5lb flue test pass
MEC19-04197 Final9/27/201910/1/201910/1/2019 3:24:25 PMPPASS
Contact Robert (QHC) @ ###-#### or QHC Office @ Phone #: ###-#### Inspection requested via web by Kevin Pratley- 2 tube heater and gas piping final ok
MEC19-04264 Final9/25/201910/1/201910/1/2019 2:52:06 PMPPASS
Please call Dave to ensure install is complete. Thank you! ###-#### Phone #: ###-#### Inspection requested via web by Rick Borg- furnace a/c coil co ok
MEC19-03412 Final10/1/201910/1/201910/1/2019 2:24:06 PMPPASS
bath fan light combo ok
MEC19-03258 Final10/1/201910/1/201910/1/2019 2:23:09 PMPPASS
Customer Contact: Michelle ###-####
HVAC Contact: Jeremy ###-#### Phone #: ###-#### Inspection requested via web by Arielle Hendricks- 2 head mini split ok in garage
MEC19-04137 Rough-in10/1/201910/1/201910/1/2019 1:59:03 PMPPART
Dryer vent inspection Phone #: ###-#### Inspection requested via web by RaChelle Frisbee- dryer duct in wall ok to cover- will look at roof penetration and duct above ceiling on next R/I inspection
MEC19-04246 Conference10/1/201910/1/201910/1/2019 1:36:25 PMPPASS
Phone #: 2088718789 >> Inspection requested via mobile web by Albert- light test hood connection ok- ok for firewrap
MEC19-04246 Pressure Test10/1/201910/1/201910/1/2019 1:35:54 PMPPASS
Phone #: 2088718789 >> Inspection requested via mobile web by Albert- 60lb gas pass
MEC17-03568 Final10/1/201910/1/201910/1/2019 12:54:56 PMPPASS
Barbara Phone #: ###-####- gas piping and fireplace were omitted on this job- R/I ok
MEC17-03568 Final10/1/201910/1/201910/1/2019 12:54:26 PMPPASS
Barbara Phone #: ###-####- final ok- gas piping was omitted on this job-
MEC19-03400 Conference10/1/201910/1/201910/1/2019 12:29:42 PMPPASS
12-1 Duct Blast Inspection requested via web by Konrad Swartz- duct blast test pass
MEC19-03399 Conference10/1/201910/1/201910/1/2019 12:29:12 PMPPASS
duct blast test pass
MEC19-03398 Conference10/1/201910/1/201910/1/2019 12:28:06 PMPCANC
12-1 Duct Blast Inspection requested via web by Konrad Swartz- wrong address for duct blast
MEC19-03985 Pressure Test9/30/201910/1/201910/1/2019 12:00:41 PMPPASS
Phone #: ###-#### Inspection requested via web by Gary Reeves- 20lb gas pass- tagged meter location
MEC19-03985 Rough-in10/1/201910/1/201910/1/2019 12:00:20 PMPPASS
Phone #: ###-#### Inspection requested via web by Gary Reeves- R/I ok
MEC19-04326 Rough-in10/1/201910/1/201910/1/2019 11:36:40 AMPCANC
Phone #: ###-#### Inspection requested via web by Oleg Chervak- wont be ready y time i come back by- reschedule
MEC19-04327 Rough-in10/1/201910/1/201910/1/2019 11:36:15 AMPCANC
Phone #: ###-#### Inspection requested via web by Oleg Chervak- wont be ready by time i come back by- reschedule
MEC19-04326 Pressure Test10/1/201910/1/201910/1/2019 11:35:48 AMPCANC
Phone #: ###-#### Inspection requested via web by Oleg Chervak- already completed
MEC19-04326 Rough-in9/30/201910/1/201910/1/2019 11:35:27 AMAFAIL
Phone #: ###-#### Inspection requested via web by Oleg Chervak-
1- need ladder provided by contractor to access furnace in attic
2- framing needs completed around b vent 2nd floor and draftstop installled
3- exhaust fan 2nd floor shall terminate 4 feet from property line
4- need to insulate bare metal in att supply and r/a
5- need to seal dryer duct to termination box
6- need 6" fresh air installed and maintain 10 feet from exhaust ducts
7- flue shall be b vent off furnace remove single wall pipe/fitting
left notice
MEC19-04326 Pressure Test9/30/201910/1/201910/1/2019 11:32:20 AMAPASS
Phone #: ###-#### Inspection requested via web by Oleg Chervak- 20lb gas pass tagged meter location
MEC19-04327 Rough-in9/30/201910/1/201910/1/2019 11:20:53 AMAFAIL
Phone #: ###-#### Inspection requested via web by Oleg Chervak-
1- framing needs completed around b vent 2nd floor and draftstop installed correctly
2- dryer duct to termination box needs sealed
3- need 6" fresh air ran and maintain 10 feet from exhaust
4- exhaust fan shall terminate 4 feet from property line 2nd flood
5 need all bare metal in attic insulated off furnace supply and R/A
MEC19-04327 Pressure Test9/30/201910/1/201910/1/2019 11:16:18 AMAPASS
Phone #: ###-#### Inspection requested via web by Oleg Chervak- 20lb gas pass- tagged meter location
MEC19-04312 Final9/30/201910/1/201910/1/2019 11:05:12 AMPPASS
Please call Craig on your way - ###-#### Phone #: ###-#### Inspection requested via web by Arielle Hendricks- a/c coil co ok
MEC19-04321 Final9/30/201910/1/201910/1/2019 10:35:33 AMAFAIL
THIS INSPECTION IS FOR ROUGHIN/FINAL , PLEASE CALL GLEN WITH ANY QUESTIONS Phone #: ###-#### Inspection requested via web by Yvonne Bowman- need to add wet switch to 3 secondarys at coil location- need uv protection outside at lineset and seal all lineset penetrations weather tight- need to check valuation since 3 furnaces coils and a/cs were installed not RTU as listed
MEC19-04159 Rough-in9/28/201910/1/201910/1/2019 10:17:28 AMAFAIL
Call 1/2 hour prior for homeowner to meet you at the home. Thanks Phone #: ###-#### Inspection requested via web by Rene Neumeyer- draft stop needs framed in exterior wall- need gas shut off accessable at fireplace is dante valve being used ??
MEC19-04331 Rough-in9/30/201910/1/201910/1/2019 9:38:43 AMAPASS
PHYLLIS ###-#### Phone #: ###-#### Inspection requested via web by Mike Almanza- R/I ok
MEC19-04331 Final10/1/201910/1/201910/1/2019 9:38:26 AMAPASS
PHYLLIS ###-#### Phone #: ###-#### Inspection requested via web by Mike Almanza- fireplace final ok
MEC19-04331 Pressure Test9/30/201910/1/201910/1/2019 9:38:01 AMAPASS
PHYLLIS ###-#### Phone #: ###-#### Inspection requested via web by Mike Almanza- 20lb gas pass- need to firecaulk gas penetration inside garage at furnace location thru floor
MEC19-04319 Final10/1/201910/1/201910/1/2019 9:22:05 AMAPASS
Inspection requested via web by Floyd Floyd Peek- insulation flex and registers ok- final ok- card signed
MEC19-04137 Rough-in9/30/201910/1/201910/1/2019 9:04:26 AMACANC
Dryer vent inspection Phone #: ###-#### Inspection requested via web by RaChelle Frisbee- no dryer duct installed- talked with contractor- will reschedule
MEC19-03443 Final9/27/201910/1/201910/1/2019 8:47:27 AMACANC
JOB CONTACT - AB ###-#### Phone #: ###-#### Inspection requested via web by BECCA DUMMER- bld under review- need plan mod excepted and new approved prints from plan mod onsite for inspection
MEC19-03450 Final9/30/201910/1/201910/1/2019 8:26:28 AMAPASS
David is homeowner (number provided). Please give him a heads up when you are on your way to ensure he is home. He should be there, though. If you run into any issues, please call Alyssa at ###-####. Phone #: ###-#### Inspection requested via web by Alyssa Cromwell- final ok
MEC19-03404 Conference9/30/201910/1/201910/1/2019 8:04:18 AMPCANC
12-1 Duct Blast Air Balance on 2 units >> Inspection requested via web by Konrad Swartz Inspection cancelled from web by: Konrad Swartz
MEC19-00907 Mec-Aging Inspection10/1/201910/1/201910/1/2019 7:51:53 AM FAIL
contractor needs to schedule inspection if works complete- permit will expire next aging if no activity