Inspections for the day of: Friday, October 10, 2003.
Number of inspections: 14
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRick Jackson
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR03-00381 FIR-Aging Inspection10/10/200310/10/200310/10/2003 12:00:00 AM PASS
wip 10/10/2003 9:26:40 AM
FIR03-00555 INSP-Supply line flush10/9/200310/10/200310/10/2003 12:00:00 AMACANC
Scheduled by a contractor via Hello! on 10/9/2003 at 12:42:30 PM. Contact: ###-####. see fir03-00376 10/10/2003 9:18:45 AM
BLD03-01913 FIRE-Conference10/9/200310/10/200310/10/2003 12:00:00 AMAPART
larry; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie met with Larry and talked about the need to get alarm plans submitted for the new type I hood; panel will require smoke detector above panel; Dave Miller will have to approve a temp occupancy 10/10/2003 2:54:17 PM
BLD02-02962 BLD-Final10/9/200310/10/200310/10/2003 12:00:00 AMAPASS
I have the co card call me. 301
BLD02-02569 FIRE-Final Inspection10/9/200310/10/200310/10/2003 12:00:00 AMAPASS
Scheduled by a contractor via Hello! on 10/9/2003 at 4:50:05 PM. Contact: ###-####. the owner was in process of lowering the shelves to comply with approved plans instead of resubmitting for changes; will have completed for sturctural inspector 10/10/2003 8:49:03 AM
BLD03-01373 FIRE-Conference10/9/200310/10/200310/10/2003 12:00:00 AMAPART
Scheduled by a contractor via Hello! on 10/9/2003 at 6:21:36 PM. Contact: ###-####. met with GC about fire extinguisher placement; will talk to Troy and Sam 10/10/2003 11:39:44 AM
FIR03-00014 INSP-Final Inspection10/8/200310/10/200310/10/2003 12:00:00 AMAFAIL
Would like inspection at 8:00AM, clinic has surgery all other times of the day; Phone #: ###-#### Internet Inspection Request from: Robert Bailey exsisting horn/strobes are not temporal tone and have frosted strobes; manual pulls above 48 inches 10/10/2003 8:33:02 AM
FIR03-00376 INSP-Supply line flush10/10/200310/10/200310/10/2003 12:00:00 AMANR
attempted to flush but a limited amount of water flowed with valve wide open; checked plans and there is another valve upstream on the eastside of Cloverdale that may be partially closed 10/10/2003 4:03:28 PM
BLD02-02962 FIRE-Final Inspection10/10/200310/10/200310/10/2003 12:00:00 AMAPASS
FIR03-00431 INSP-Final Inspection10/8/200310/10/200310/10/2003 12:00:00 AMPFAIL
Would like inspection after 3:00PM, school will be out; Phone #: ###-#### Internet Inspection Request from: Robert Bailey smoke/fire dampers were closed so the detector controlling dampers couldn't be verified; need display descriptor for the detectors to show on the FACP; update maps 10/10/2003 4:00:50 PM
BLD03-00454 FIRE-Final Inspection10/10/200310/10/200310/10/2003 12:00:00 AMPPASS
nick; Phone #: ###-#### Internet Inspection Request from: Annette Moore doors not latching and they will have for structural inspector 10/10/2003 1:10:37 PM
FIR03-00582 INSP-Final Inspection10/10/200310/10/200310/10/2003 12:00:00 AMPPASS
LES; Phone #: ###-#### Internet Inspection Request from: Annette Moore
FIR03-00578 INSP-Final Inspection10/10/200310/10/200310/10/2003 12:00:00 AMPPASS
LES; Phone #: ###-#### Internet Inspection Request from: Annette Moore
FIR03-00529 INSP-Sprinkler Rough-in/Hydro10/10/200310/10/200310/10/2003 12:00:00 AMPFAIL
ERIC; Phone #: ###-#### Internet Inspection Request from: Annette Moore combustible cavity around/under fireplace requires protection or make it noncombustible; draft stop penetrations; insulation on heads in attic area; minor changes made to rooms on east side to prevent overspacing; hydro on overhead okay 10/10/2003 12:26:39 PM