BLD03-01619
| FIRE-Final Inspection | 10/10/2003 | 10/10/2003 | 10/10/2003 12:00:00 AM | A | PASS |
|
|
Fire life safety OK
|
FIR03-00498
| INSP-Alarm Testing | 10/8/2003 | 10/10/2003 | 10/10/2003 12:00:00 AM | A | PASS |
|
|
MATT; Phone #: ###-#### Internet Inspection Request from: Annette Moore
|
FIR03-00270
| INSP-Final Inspection | 10/9/2003 | 10/10/2003 | 10/10/2003 12:00:00 AM | P | CANC |
|
|
Scheduled by a contractor via Hello! on 10/9/2003 at 2:21:06 PM. Contact: ###-####.
|
FIR03-00270
| INSP-Final Inspection | 10/9/2003 | 10/10/2003 | 10/10/2003 12:00:00 AM | P | CANC |
|
|
Scheduled by a contractor via Hello! on 10/9/2003 at 2:21:06 PM. Contact: ###-####.
|
BLD02-02719
| FIRE-Final Inspection | 10/10/2003 | 10/10/2003 | 10/10/2003 12:00:00 AM | P | PART |
|
|
Temp occupancy given until the NAC panel for the fire alarm system can be replaced
|
BLD02-01069
| FIRE-Final Inspection | 10/10/2003 | 10/10/2003 | 10/10/2003 12:00:00 AM | P | PART |
|
|
Temp occupancy given until the NAC panel for the fire alarm system can be replaced
|
BLD02-02720
| FIRE-Final Inspection | 10/10/2003 | 10/10/2003 | 10/10/2003 12:00:00 AM | P | PART |
|
|
Temp occupancy given until the NAC panel for the fire alarm system can be replaced
|
BLD02-01070
| FIRE-Final Inspection | 10/10/2003 | 10/10/2003 | 10/10/2003 12:00:00 AM | P | PART |
|
|
Temp occupancy given until the NAC panel for the fire alarm system can be replaced
|
FIR03-00268
| INSP-Final Inspection | 10/10/2003 | 10/10/2003 | 10/10/2003 12:00:00 AM | P | PART |
|
|
NAC panels had to be replaced due to excessive current draw. Manufacture sent out a temp. replacement panel that still draws more power than original design. New panels will be in within 5 days. The panels installed require 7.6 ah batteries to meet code. 7 ah are installed.
|
FIR03-00277
| INSP-Final Inspection | 10/10/2003 | 10/10/2003 | 10/10/2003 12:00:00 AM | P | PART |
|
|
NAC panels had to be replaced due to excessive current draw. Manufacture sent out a temp. replacement panel that still draws more power than original design. New panels will be in within 5 days. The panels installed require 7.6 ah batteries to meet code. 7 ah are installed.
|