Inspections for the day of: Monday, October 10, 2005.
Number of inspections: 9
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE05-03241 Electrical Rough-In10/10/200510/10/200510/10/2005 4:10:20 PMPPASS
Scheduled by a contractor via Hello! on 10/10/2005 at 8:49:03 AM. Contact: ###-####. ceiling cover ok , left sticker
ELE05-03695 Temporary Service10/10/200510/10/200510/10/2005 4:05:39 PMPFAIL
###-#### - dan called contr, left message, left corr notice, fee due, 312.5 conductors entering enclosures shall be protected from abrasion, 408.4 circuit directory shall be provided, BCC job id sticker shall be provided
ELE05-02589 Final10/10/200510/10/200510/10/2005 1:47:14 PMPFAIL
Phone #: ###-#### Internet Inspection Request from: Tyler Bowen called contr, left corr notice, 210.52(E) recpt shall be installed at front of dwelling, 250.68(A) gec connection shall be accessible, 408.4 circuit directory shall be correct, 210.11(C)(3) bathroom recpt shall be on 20a circuit, 404.4 outside switches shall be in weatherproof enclosure
ELE05-03104 Final10/7/200510/10/200510/10/2005 10:22:33 AMACANC
chris; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa see conf
ELE05-03007 Final10/8/200510/10/200510/10/2005 9:58:54 AMAPASS
Charlie; Phone #: ###-#### Internet Inspection Request from: Melyne Davis ok to final
ELE05-03343 Final10/6/200510/10/200510/10/2005 9:23:57 AMAPASS
trent; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa called contr, left survey, 408.4 panelboard schedule shall be complete, 110.3 gfci to right of sink shall trip, 250.104(A) metal water piping shall be bonded, hot to cold, signed struct card
ELE05-03008 Final10/8/200510/10/200510/10/2005 8:44:55 AMAFAIL
Charlie; Phone #: ###-#### Internet Inspection Request from: Melyne Davis 406.4(D) receptacles shall be flush or project from faceplates, 110.3 equipment shall be installed for it's use: mbr light switch trips afci, laundry room switching not correct
ELE05-02740 Final10/8/200510/10/200510/10/2005 8:37:56 AMAFAIL
Charlie; Phone #: ###-#### Internet Inspection Request from: Melyne Davis called contr, left corr notice, 406.4(D) recpts shall be flush or project from faceplate(laundry) 406.5 faceplate shall seat against mounting surface(front gfci outdoor) 408.4 panelboard schedule shall be legible, 110.3 dishwasher shall be wired
ELE05-03104 Conference10/10/200510/10/200510/10/2005 12:00:00 AMADONE
chris; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa met with general, they are still at least 1 week out. Told them they need to be all but done before they ask for t/o