Inspections for the day of: Monday, October 10, 2005.
Number of inspections: 13
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR05-00562 INSP-Sprinkler Rough-in/Hydro10/10/200510/10/200510/10/2005 4:32:09 PMPFAIL
Can not do a final as the sprinkler plans need to be resubmitted. Sprinkler piping is ok to cover in the new area.
FIR05-00562 INSP-Final Inspection10/10/200510/10/200510/10/2005 4:31:50 PMPFAIL
Can not do a final as the sprinkler plans need to be resubmitted. Sprinkler piping is ok to cover in the new area.
BLD05-01608 FIRE-Final Inspection10/7/200510/10/200510/10/2005 4:30:33 PMPFAIL
Inspection was actually for a conference. I went over life safety items with the contractor. This included providing an additional exit sign at the bottom of the stairs with approved door hardware on the second exit to the exterior stairway. Also needs automatic flush bolts on the main entry exit. The two interior doors that lead into the main exit lobby require approved door hardware unless plan review is ok with the thumbturn deadbolts. Fire extinguishers will be required on both levels as well.
FIR05-00210 INSP-Alarm Testing10/10/200510/10/200510/10/2005 4:27:03 PMPFAIL
Fire alarm contractor and the electrical contractor where unable to provide a voltage meter to measure standby battery requirements and did not have a telephone butt set for verification that two phone lines had been provided. I stopped test. No items inspected.
FIR04-00750 INSP-Sprinkler Rough-in/Hydro10/10/200510/10/200510/10/2005 3:13:06 PMPPASS
Hydro test for the outside canopy passed.
MIS05-00179 FIR-Final10/10/200510/10/200510/10/2005 3:11:55 PMPPASS
Life safety finaled
BLD04-02934 FIRE-Final Inspection10/10/200510/10/200510/10/2005 1:43:23 PMPFAIL
fire sprinkler plans are still in review and fire alarm failed. No life safety inspection performed.
MIS05-00136 FIR-Final10/10/200510/10/200510/10/2005 1:37:23 PMPPART
A temporary occupancy was given. Need max. occupant load sign for "98". Provide exit signs/emergency lights as discussed and marked on the plans. Repair the exit sign to the prep area. Mount fire extinguisher at point of sale and lower fire extinguisher in the kitchen. Panic hardware is required at main exit per review comments.
BLD04-02934 FIRE-Final Inspection10/7/200510/10/200510/10/2005 12:13:17 PMAFAIL
fire sprinkler plans are still in review and fire alarm failed. No life safety inspection performed.
BLD05-01523 FIRE-Final Inspection10/7/200510/10/200510/10/2005 11:56:51 AMAFAIL
ken; Phone #: ###-####
Provide approved door hardware on both exit doors and tag the fire extinguisher.
BLD05-02082 FIRE-Final Inspection10/7/200510/10/200510/10/2005 10:41:18 AMAFAIL
Tag fire extinguisher in lobby and test duct smoke detectors
FIR05-00316 INSP-Final Inspection10/7/200510/10/200510/10/2005 10:10:39 AMAFAIL
Only tested the phone lines and three tamper switches. Phone lines had to be repaired as I waited. A meter had to be found for testing batteries but it didn't work. The supervisory points received at the central station do not match plans. Need to test all devices. Need security to the outlet on same circuti to the facp.
BLD05-02607 FIRE-Final Inspection10/7/200510/10/200510/10/2005 10:07:55 AMAFAIL
The storage room needs approved hardware on all doors, fire extinguisher, test smoke evac system, ceiling installed and sprinkler pendant coverage corrected. Retail area needs a very short time line in writing that a new tenant is moving in or ceiling and sprinkler modifications performed. Also need to test the smoke evac system.