Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE08-02762 Electrical Rough-In10/10/200810/10/200810/10/2008 4:07:27 PMPPASS
John see guys on site Phone #: ###-#### ok to cover bath in shop area, no esc this project
ELE08-02763 Electrical Rough-In10/10/200810/10/200810/10/2008 3:43:13 PMPPASS
John see guys on site Phone #: ###-#### ric ok room in shop, no esc this project
ESC07-00152 General Inspection10/10/200810/10/200810/10/2008 3:06:15 PMPPASS
looked ok
ESC08-00155 General Inspection10/10/200810/10/200810/10/2008 3:05:26 PMPPASS
looked ok
ESC08-00807 General Inspection10/10/200810/10/200810/10/2008 3:04:42 PMPNH
nh, could not access area
ESC08-00504 General Inspection10/10/200810/10/200810/10/2008 3:03:44 PMPPASS
looked ok
ESC08-00717 General Inspection10/10/200810/10/200810/10/2008 3:02:44 PMAPASS
looked ok
ESC07-01432 General Inspection10/10/200810/10/200810/10/2008 3:01:47 PMAPASS
looked ok
ELE08-02623 Final10/9/200810/10/200810/10/2008 3:00:54 PMPNH
Phone #: ###-#### Internet Inspection Request from: Jenni Keller called left noyice,said to call when available, fee due
ELE08-01901 Electrical Rough-In10/10/200810/10/200810/10/2008 2:24:02 PMPPASS
Please inspect underground conduit from building to parking lot lights. Thanks Phone #: ###-#### Internet Inspection Request from: ERIC CENTERS ok to cover u/g across parking lot
ELE08-02750 Permanent Service10/9/200810/10/200810/10/2008 2:14:12 PMPNR
final to check disconnects for proper marking Phone #: ###-#### Internet Inspection Request from: joe wheeler met user, explained that he has to get bld for occupancy, called contractor and said would do inspection after permits are tied together, tol user he has until early next week, like Tuesday to get bld no esc this project
ELE08-01632 Electrical Rough-In10/9/200810/10/200810/10/2008 1:25:02 PMPFAIL
Phone #: ###-#### Internet Inspection Request from: Jenni Keller called left correction notice, NEC 300.4(A) edge of bored holes shall be 1 1/4" from edge of framing members, 300.14 there shall be minimum 6" free conductor left in box before splice, 314.17(C) nm cable shall be secured within 8" of boxes, 334.30 nm shall be secured within 12" of panel, 314.20 boxes shall be flush with finished surface in combustible walls, 210.52(A)(1),(2) receptacles shall be such that no point along floor line is over 6' from an outlet; any space over 2' shall be counted as wall space, 210.52(C)(1) countertop receptacles shall be spaced such that no outlet is over 2' from another outlet, BCC approved set of plans shall be on job,all make-up shall be done, shall change room count to 23 rooms on permit
ELE07-03457 Electrical Rough-In10/10/200810/10/200810/10/2008 12:19:31 PMPPART
partial underground inspection please-joe Phone #: ###-#### skilled nursing courtyard u/g ok to cover
ELE08-02757 Rough-In Permanent Service10/9/200810/10/200810/10/2008 10:52:11 AMAPASS
###-####- Darren ric ok, p/s u/g n ok
ELE08-02737 Final10/8/200810/10/200810/10/2008 10:25:29 AMAPART
contact: Eric Stewart Phone #: ###-#### Internet Inspection Request from: Deb Gooden installation looks ok, need to see listing, called contractor, will get back to city, no esc this project
ELE08-02759 Conference10/9/200810/10/200810/10/2008 9:47:55 AMADONE
gene Phone #: ###-#### met electrician, talked about taking walls down to inspect work done without permit, no esc this project
ELE08-02423 Electrical Rough-In10/9/200810/10/200810/10/2008 8:45:53 AMAPASS
JASON BLD 3 L2 UNITS C, A2, C2, D1 & B1 Phone #: ###-#### Internet Inspection Request from: Sean DeLacy ok to cover 5 units 2nd floor anop