ELE08-02762
| Electrical Rough-In | 10/10/2008 | 10/10/2008 | 10/10/2008 4:07:27 PM | P | PASS |
|
|
John see guys on site Phone #: ###-#### ok to cover bath in shop area, no esc this project
|
ELE08-02763
| Electrical Rough-In | 10/10/2008 | 10/10/2008 | 10/10/2008 3:43:13 PM | P | PASS |
|
|
John see guys on site Phone #: ###-#### ric ok room in shop, no esc this project
|
ESC07-00152
| General Inspection | 10/10/2008 | 10/10/2008 | 10/10/2008 3:06:15 PM | P | PASS |
|
|
looked ok
|
ESC08-00155
| General Inspection | 10/10/2008 | 10/10/2008 | 10/10/2008 3:05:26 PM | P | PASS |
|
|
looked ok
|
ESC08-00807
| General Inspection | 10/10/2008 | 10/10/2008 | 10/10/2008 3:04:42 PM | P | NH |
|
|
nh, could not access area
|
ESC08-00504
| General Inspection | 10/10/2008 | 10/10/2008 | 10/10/2008 3:03:44 PM | P | PASS |
|
|
looked ok
|
ESC08-00717
| General Inspection | 10/10/2008 | 10/10/2008 | 10/10/2008 3:02:44 PM | A | PASS |
|
|
looked ok
|
ESC07-01432
| General Inspection | 10/10/2008 | 10/10/2008 | 10/10/2008 3:01:47 PM | A | PASS |
|
|
looked ok
|
ELE08-02623
| Final | 10/9/2008 | 10/10/2008 | 10/10/2008 3:00:54 PM | P | NH |
|
|
Phone #: ###-#### Internet Inspection Request from: Jenni Keller called left noyice,said to call when available, fee due
|
ELE08-01901
| Electrical Rough-In | 10/10/2008 | 10/10/2008 | 10/10/2008 2:24:02 PM | P | PASS |
|
|
Please inspect underground conduit from building to parking lot lights. Thanks Phone #: ###-#### Internet Inspection Request from: ERIC CENTERS ok to cover u/g across parking lot
|
ELE08-02750
| Permanent Service | 10/9/2008 | 10/10/2008 | 10/10/2008 2:14:12 PM | P | NR |
|
|
final to check disconnects for proper marking Phone #: ###-#### Internet Inspection Request from: joe wheeler met user, explained that he has to get bld for occupancy, called contractor and said would do inspection after permits are tied together, tol user he has until early next week, like Tuesday to get bld no esc this project
|
ELE08-01632
| Electrical Rough-In | 10/9/2008 | 10/10/2008 | 10/10/2008 1:25:02 PM | P | FAIL |
|
|
Phone #: ###-#### Internet Inspection Request from: Jenni Keller called left correction notice, NEC 300.4(A) edge of bored holes shall be 1 1/4" from edge of framing members, 300.14 there shall be minimum 6" free conductor left in box before splice, 314.17(C) nm cable shall be secured within 8" of boxes, 334.30 nm shall be secured within 12" of panel, 314.20 boxes shall be flush with finished surface in combustible walls, 210.52(A)(1),(2) receptacles shall be such that no point along floor line is over 6' from an outlet; any space over 2' shall be counted as wall space, 210.52(C)(1) countertop receptacles shall be spaced such that no outlet is over 2' from another outlet, BCC approved set of plans shall be on job,all make-up shall be done, shall change room count to 23 rooms on permit
|
ELE07-03457
| Electrical Rough-In | 10/10/2008 | 10/10/2008 | 10/10/2008 12:19:31 PM | P | PART |
|
|
partial underground inspection please-joe Phone #: ###-#### skilled nursing courtyard u/g ok to cover
|
ELE08-02757
| Rough-In Permanent Service | 10/9/2008 | 10/10/2008 | 10/10/2008 10:52:11 AM | A | PASS |
|
|
###-####- Darren ric ok, p/s u/g n ok
|
ELE08-02737
| Final | 10/8/2008 | 10/10/2008 | 10/10/2008 10:25:29 AM | A | PART |
|
|
contact: Eric Stewart Phone #: ###-#### Internet Inspection Request from: Deb Gooden installation looks ok, need to see listing, called contractor, will get back to city, no esc this project
|
ELE08-02759
| Conference | 10/9/2008 | 10/10/2008 | 10/10/2008 9:47:55 AM | A | DONE |
|
|
gene Phone #: ###-#### met electrician, talked about taking walls down to inspect work done without permit, no esc this project
|
ELE08-02423
| Electrical Rough-In | 10/9/2008 | 10/10/2008 | 10/10/2008 8:45:53 AM | A | PASS |
|
|
JASON BLD 3 L2 UNITS C, A2, C2, D1 & B1 Phone #: ###-#### Internet Inspection Request from: Sean DeLacy ok to cover 5 units 2nd floor anop
|