MEC16-04268
| Pressure Test | 10/10/2016 | 10/10/2016 | 10/10/2016 4:21:21 PM | P | PASS |
|
|
door code 0152 Phone #: ###-#### Inspection requested via web by Bryan Palmer - 60lb gas pass
|
MEC15-04483
| Mec-Aging Inspection | 10/10/2016 | 10/10/2016 | 10/10/2016 3:36:41 PM | | DONE |
|
|
Expired
|
MEC15-04483
| DOC - Permit Expired | 10/10/2016 | 10/10/2016 | 10/10/2016 3:36:27 PM | P | PASS |
|
|
|
MEC15-05714
| Mec-Aging Inspection | 10/10/2016 | 10/10/2016 | 10/10/2016 3:11:00 PM | | CANC |
|
|
|
MEC16-02191
| Rough-in | 10/10/2016 | 10/10/2016 | 10/10/2016 2:10:56 PM | P | FAIL |
|
|
BJ ###-####. fresh air can only be seen from up above on the deck. they terminate sidewall. the exhaust terminates thru the roof. Please cal lif yo uwant me to meet you out there Inspection requested via web by william kerwin - Need to support and strap line sets, need to replace hangers that were taken down, Need to seal duct joints on exhaust.
|
MEC16-04491
| Rough-in | 10/10/2016 | 10/10/2016 | 10/10/2016 2:09:30 PM | P | PASS |
|
|
bj ###-#### please call me if any questions. have sent over the ductwork review and should have a n engineer letter back anytime. Inspection requested via web by william kerwin
|
MEC16-04491
| Pressure Test | 10/10/2016 | 10/10/2016 | 10/10/2016 2:08:57 PM | P | FAIL |
|
|
bj ###-#### Inspection requested via web by william kerwin - pressure down to 38lbs
|
MEC16-00234
| Mec-Aging Inspection | 10/10/2016 | 10/10/2016 | 10/10/2016 11:48:28 AM | | CANC |
|
|
|
MEC15-02759
| Final | 10/7/2016 | 10/10/2016 | 10/10/2016 10:58:47 AM | A | PART |
|
|
Final inspection for VRT, including boiler flue rework. All documents will be emailed to Chad S. Phone #: ###-#### Inspection requested via web by Melissa Kaae - temporary occupancy of the VRT space okay
|
MEC16-03714
| Final | 10/7/2016 | 10/10/2016 | 10/10/2016 10:58:10 AM | A | PART |
|
|
Final mech inspection for VRT TI, including boiler flue rework. All documents will be emailed to Chad S. Phone #: ###-#### Inspection requested via web by Melissa Kaae - Boiler flues okay. temporary occupancy okay.
|
MEC16-02295
| Rough-in | 10/7/2016 | 10/10/2016 | 10/10/2016 10:57:08 AM | A | PASS |
|
|
Rough-in cover. Onsite contact: Trever Jensen. Phone #: ###-#### Inspection requested via web by Melissa Kaae - okay to cover
|
MEC16-04435
| Rough-in | 10/7/2016 | 10/10/2016 | 10/10/2016 9:27:07 AM | A | PASS |
|
|
duct blast at 9 am Phone #: ###-#### Inspection requested via web by Marisa Hone
|
MEC16-04435
| Pressure Test | 10/7/2016 | 10/10/2016 | 10/10/2016 9:26:53 AM | A | PASS |
|
|
duct blast at 9 am Phone #: ###-#### Inspection requested via web by Marisa Hone - 20lb gas, duct blast pass
|
MEC16-04450
| Rough-in | 10/10/2016 | 10/10/2016 | 10/10/2016 9:26:22 AM | A | PASS |
|
|
|
MEC16-02829
| Final | 10/5/2016 | 10/10/2016 | 10/10/2016 8:38:00 AM | A | PASS |
|
|
Please inspect first thing in AM. Homeowner is Judy Pope 3###-#### or ###-#### Phone #: ###-#### Inspection requested via web by Mary LaFayette
|