Inspections for the day of: Tuesday, October 10, 2017.
Number of inspections: 8
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR17-00188 INSP-Final Inspection10/4/201710/10/201710/10/2017 12:24:13 PMPCANC
Eric Phone #: ###-####
BLD17-02917 FIRE-Final Inspection10/9/201710/10/201710/10/2017 12:19:45 PMPPASS
Life safety passed.

Jason Allen Phone #: ###-####
BLD16-03749 FIRE-Final Inspection10/9/201710/10/201710/10/2017 12:18:31 PMPFAIL
The plans on site are not the city approved. No inspection performed.

Phone #: ###-#### Inspection requested via web by Curtis Bodenbender
BLD16-03883 FIRE-Final Inspection10/9/201710/10/201710/10/2017 10:19:09 AMAFAIL
Need the city approved plans, need building address, need stickers at doors, need tags on fire extinguishers. Emergency lights and exit signs tested ok.

Ken Phone #: ###-####
BLD16-02147 FIRE-Final Inspection10/10/201710/10/201710/10/2017 9:06:30 AMPFAIL
Need the city approved drawings and verification that the Opticon is functional for the gates.
FIR17-00432 INSP-Supply line flush10/9/201710/10/201710/10/2017 9:05:15 AMAPASS
Underground supply line flush passed
FIR17-00582 INSP-Final Inspection10/10/201710/10/201710/10/2017 8:11:43 AMPPASS
Permit finaled
FIR17-00582 INSP-Sprinkler Rough-in/Hydro10/9/201710/10/201710/10/2017 7:38:09 AMACANC
Wrong inspection type scheduled and wrong suite number.

Stan Phone #: ###-####