Inspections for the day of: Friday, October 11, 2002.
Number of inspections: 12
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR02-00368 INSP-Final Inspection10/7/200210/11/200210/11/2002 12:00:00 AMAPASS
fire alarm finaled 10/11/2002 10:25:06 AM
FIR02-00369 INSP-Final Inspection10/7/200210/11/200210/11/2002 12:00:00 AMAFAIL
install covers on the A/V's. Change the A/V mounted in the ceiling to a listed ceiling device or relocate to the wall 10/11/2002 10:30:49 AM
FIR02-00383 INSP-Final Inspection10/7/200210/11/200210/11/2002 12:00:00 AMAFAIL
provide 12AH batteries or verify the existing 10ah batteries are OK to remain, repair A/V 4-13 10/11/2002 10:29:04 AM
BLD02-01256 FIRE-Final Inspection10/9/200210/11/200210/11/2002 12:00:00 AMAFAIL
provide approved door hardware for the restroom and cubicle . Turn exit sign at the east exit 10/11/2002 10:26:35 AM 10/11/2002 10:27:01 AM
FIR02-00314 INSP-Final Inspection10/10/200210/11/200210/11/2002 12:00:00 AMAPASS
fire sprinklers finaled 10/11/2002 10:50:25 AM
FIR02-00151 INSP-Final Inspection10/11/200210/11/200210/11/2002 12:00:00 AMAPASS
fire alarm finaled
BLD01-02575 FIRE-Final Inspection10/11/200210/11/200210/11/2002 12:00:00 AMAPASS
fire life/safety finaled
BLD02-01028 FIRE-Alarm Testing10/10/200210/11/200210/11/2002 12:00:00 AMPPASS
Inspection was for the kitchen hood system. The hood operated properly with all caps blowing off, power, gas and make up air shutting off 10/11/2002 3:06:01 PM
BLD02-01600 FIRE-Final Inspection10/11/200210/11/200210/11/2002 12:00:00 AMPPART
sprinkler piping is OK to cover 10/11/2002 3:29:32 PM
BLD01-02963 FIRE-Final Inspection10/11/200210/11/200210/11/2002 12:00:00 AMPPASS
life safety finaled 10/11/2002 2:01:28 PM
BLD01-02962 FIRE-Final Inspection10/11/200210/11/200210/11/2002 12:00:00 AMPPASS
###-#### life safety finaled 10/11/2002 2:01:40 PM
BLD01-02961 FIRE-Final Inspection10/11/200210/11/200210/11/2002 12:00:00 AMPPASS
###-#### life safety finaled 10/11/2002 2:01:51 PM