FIR04-00436
| INSP-Sprinkler Rough-in | 10/7/2004 | 10/11/2004 | 10/11/2004 12:00:00 AM | A | PART |
|
|
joe; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles Reviewed plans with Dirk as they want to make changes to the point of connection to the 4 inch overhead line - connection will be made inside the permitted area and not on area as shown on plans; no resubmiitals needed per Bill Alexander 10/11/2004 11:28:55 AM
|
BLD04-01781
| FIRE-Conference | 10/8/2004 | 10/11/2004 | 10/11/2004 12:00:00 AM | A | PART |
|
|
Scheduled by a contractor via Hello! on 10/8/2004 at 10:10:34 AM. Contact: ###-####. Reviewed items for final with GC 10/11/2004 9:48:52 AM
|
BLD04-01962
| FIRE-Final Inspection | 10/8/2004 | 10/11/2004 | 10/11/2004 12:00:00 AM | A | FAIL |
|
|
allen; Phone #: ###-#### Note: please call 1/2 hr prior to insepction Internet Inspection Request from: Cathy Chiles Need emergency lights per plans 10/11/2004 3:36:34 PM
|
FIR04-00588
| INSP-Sprinkler Rough-in/Hydro | 10/11/2004 | 10/11/2004 | 10/11/2004 12:00:00 AM | A | PART |
|
|
Approx. 11:00 AM Thank you Internet Inspection Request from: Trent Bice Okay to cover - straps to 2x4's between joists were used for branch lines; the anti-freeze loop was deleted as the combustible void will be filled with insulation; UG not installed as of this inspection 10/11/2004 11:26:26 AM
|
FIR02-00005
| INSP-Final Inspection | 10/11/2004 | 10/11/2004 | 10/11/2004 12:00:00 AM | P | FAIL |
|
|
brian; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles Dry system under walkway trip test okay; need straps on two hangers near stair; need air gauge at dry valve 10/11/2004 1:49:57 PM
|
FIR04-00620
| INSP-Sprinkler Rough-in/Hydro | 10/11/2004 | 10/11/2004 | 10/11/2004 12:00:00 AM | P | PASS |
|
|
Scheduled by a contractor via Hello! on 10/11/2004 at 9:49:36 AM. Contact: ###-####.
|
FIR04-00618
| INSP-Final Inspection | 10/11/2004 | 10/11/2004 | 10/11/2004 12:00:00 AM | P | PASS |
|
|
|
BLD04-01662
| FIRE-Conference | 10/11/2004 | 10/11/2004 | 10/11/2004 12:00:00 AM | P | PART |
|
|
Met with GC about the door hardware, exit sings and required exiting from this space as the exsisting door had exit sign and none to be added on the approved plans; will need architect involvement to verify exiting 10/11/2004 3:55:59 PM
|