Inspections for the day of: Tuesday, October 11, 2005.
Number of inspections: 16
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD05-02390 FIRE-Final Inspection10/11/200510/11/200510/12/2005 11:32:50 AMPPASS
Life safety finaled
FIR05-00554 INSP-Final Inspection10/11/200510/11/200510/12/2005 11:21:45 AMPPASS
Permit finaled
BLD05-02157 FIRE-Final Inspection10/11/200510/11/200510/11/2005 3:37:34 PMPFAIL
Provide additional emergency lighting in the new open office space, replace burnt out bulbs in the lights in the existing space and provide approved door hardware for the secondary exterior exit door.
FIR05-00637 INSP-Final Inspection10/11/200510/11/200510/11/2005 3:19:35 PMPPASS
Fire sprinkler permit finaled
FIR05-00655 INSP-Final Inspection10/10/200510/11/200510/11/2005 3:18:17 PMPPASS
The hood suppression system operated correctly and the signal was sent to the fire alarm panel.
FIR05-00473 INSP-Final Inspection10/10/200510/11/200510/11/2005 1:44:58 PMAFAIL
Canopies are all on but one sprinkler pendant in the northwest end of the building was installed using the small room rule. The room the pendant is in is not separated from the ajoining corridor by a wall or lintel therefore the corridor is considered part of the room which makes it exceed 800 sq. ft. An additional pendant will be required.
BLD05-00487 FIRE-Final Inspection10/10/200510/11/200510/11/2005 1:06:25 PMAFAIL
Mount max occupant load sign, Provide approved door hardware for "Store 105", provide verification of the cd rating of the temporary strobes so proper coverage can be verified and then test in the presence of the inspector. If this is done a temporary occupancy can be given by Sam Rogers permission
FIR05-00593 INSP-Sprinkler Rough-in10/10/200510/11/200510/11/2005 1:03:14 PMAFAIL
No approved plans on site. No inspection done.
FIR05-00378 INSP-Sprinkler Rough-in/Hydro10/10/200510/11/200510/11/2005 1:02:16 PMPCANC
Contact: Brian - Hydro Test; Phone #: ###-#### Internet Inspection Request from: Alicia Pauley
FIR05-00089 INSP-Sprinkler Rough-in/Hydro10/10/200510/11/200510/11/2005 12:58:58 PMPCANC
No hydro test done. Water has not been put in system yet.
FIR05-00378 INSP-Sprinkler Rough-in10/10/200510/11/200510/11/2005 12:49:47 PMAPART
Provide 200 degree pendant in the utility room, finish installing ceiling and canopies, provide longitudinal bracing on the antifreeze main under canopy. Per Bill the 130 sq. ft. max spacing is a type error. 225 sq. ft. is allowed in the light hazard areas.
FIR05-00089 INSP-Sprinkler Rough-in10/10/200510/11/200510/11/2005 12:14:37 PMAPART
I looked at the noted problems and they have been corrected. Temporary pendant heads have been installed in the west elevator lobby until the ceiling has been installed. First floor service corridor and the second floor service corridor are ok for cover.
FIR05-00566 INSP-Final Inspection10/10/200510/11/200510/11/2005 12:10:39 PMAFAIL
No test done since the fire alarm system was having problems for this end of the building and would not receive the hood alarm signal
BLD05-02082 FIRE-Final Inspection10/10/200510/11/200510/11/2005 9:00:35 AMAFAIL
Duct smoke detector mounted in the wrong position
FIR03-00279 INSP-Final Inspection10/11/200510/11/200510/11/2005 12:00:00 AMPPASS
Permit finaled 11-26-03
BLD05-00355 FIRE-Final Inspection10/10/200510/11/200510/10/2005 4:34:36 PMAPASS
Fire life safety finaled