BLD05-02390
| FIRE-Final Inspection | 10/11/2005 | 10/11/2005 | 10/12/2005 11:32:50 AM | P | PASS |
|
|
Life safety finaled
|
FIR05-00554
| INSP-Final Inspection | 10/11/2005 | 10/11/2005 | 10/12/2005 11:21:45 AM | P | PASS |
|
|
Permit finaled
|
BLD05-02157
| FIRE-Final Inspection | 10/11/2005 | 10/11/2005 | 10/11/2005 3:37:34 PM | P | FAIL |
|
|
Provide additional emergency lighting in the new open office space, replace burnt out bulbs in the lights in the existing space and provide approved door hardware for the secondary exterior exit door.
|
FIR05-00637
| INSP-Final Inspection | 10/11/2005 | 10/11/2005 | 10/11/2005 3:19:35 PM | P | PASS |
|
|
Fire sprinkler permit finaled
|
FIR05-00655
| INSP-Final Inspection | 10/10/2005 | 10/11/2005 | 10/11/2005 3:18:17 PM | P | PASS |
|
|
The hood suppression system operated correctly and the signal was sent to the fire alarm panel.
|
FIR05-00473
| INSP-Final Inspection | 10/10/2005 | 10/11/2005 | 10/11/2005 1:44:58 PM | A | FAIL |
|
|
Canopies are all on but one sprinkler pendant in the northwest end of the building was installed using the small room rule. The room the pendant is in is not separated from the ajoining corridor by a wall or lintel therefore the corridor is considered part of the room which makes it exceed 800 sq. ft. An additional pendant will be required.
|
BLD05-00487
| FIRE-Final Inspection | 10/10/2005 | 10/11/2005 | 10/11/2005 1:06:25 PM | A | FAIL |
|
|
Mount max occupant load sign, Provide approved door hardware for "Store 105", provide verification of the cd rating of the temporary strobes so proper coverage can be verified and then test in the presence of the inspector. If this is done a temporary occupancy can be given by Sam Rogers permission
|
FIR05-00593
| INSP-Sprinkler Rough-in | 10/10/2005 | 10/11/2005 | 10/11/2005 1:03:14 PM | A | FAIL |
|
|
No approved plans on site. No inspection done.
|
FIR05-00378
| INSP-Sprinkler Rough-in/Hydro | 10/10/2005 | 10/11/2005 | 10/11/2005 1:02:16 PM | P | CANC |
|
|
Contact: Brian - Hydro Test; Phone #: ###-#### Internet Inspection Request from: Alicia Pauley
|
FIR05-00089
| INSP-Sprinkler Rough-in/Hydro | 10/10/2005 | 10/11/2005 | 10/11/2005 12:58:58 PM | P | CANC |
|
|
No hydro test done. Water has not been put in system yet.
|
FIR05-00378
| INSP-Sprinkler Rough-in | 10/10/2005 | 10/11/2005 | 10/11/2005 12:49:47 PM | A | PART |
|
|
Provide 200 degree pendant in the utility room, finish installing ceiling and canopies, provide longitudinal bracing on the antifreeze main under canopy. Per Bill the 130 sq. ft. max spacing is a type error. 225 sq. ft. is allowed in the light hazard areas.
|
FIR05-00089
| INSP-Sprinkler Rough-in | 10/10/2005 | 10/11/2005 | 10/11/2005 12:14:37 PM | A | PART |
|
|
I looked at the noted problems and they have been corrected. Temporary pendant heads have been installed in the west elevator lobby until the ceiling has been installed. First floor service corridor and the second floor service corridor are ok for cover.
|
FIR05-00566
| INSP-Final Inspection | 10/10/2005 | 10/11/2005 | 10/11/2005 12:10:39 PM | A | FAIL |
|
|
No test done since the fire alarm system was having problems for this end of the building and would not receive the hood alarm signal
|
BLD05-02082
| FIRE-Final Inspection | 10/10/2005 | 10/11/2005 | 10/11/2005 9:00:35 AM | A | FAIL |
|
|
Duct smoke detector mounted in the wrong position
|
FIR03-00279
| INSP-Final Inspection | 10/11/2005 | 10/11/2005 | 10/11/2005 12:00:00 AM | P | PASS |
|
|
Permit finaled 11-26-03
|
BLD05-00355
| FIRE-Final Inspection | 10/10/2005 | 10/11/2005 | 10/10/2005 4:34:36 PM | A | PASS |
|
|
Fire life safety finaled
|