Inspections for the day of: Wednesday, October 11, 2006.
Number of inspections: 17
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE06-00847 Final10/11/200610/11/200610/11/2006 4:22:32 PMPPASS
Garage code 2208; Phone #: ###-#### Internet Inspection Request from: Joe Thomas called contr about rev polarity on kitchen and dining ckt, ok to final
ELE06-00846 Final10/11/200610/11/200610/11/2006 4:01:58 PMPPASS
Garage code 2208; Phone #: ###-#### Internet Inspection Request from: Joe Thomas called contr to finish panel schedule, and add bkr lo for dw, ok to final
ELE06-02672 Final10/9/200610/11/200610/11/2006 3:26:05 PMPNH
Work performed by Matthew White. Internet Inspection Request from: Matt Santacruz called contr, left card
ELE04-00041 Conference10/10/200610/11/200610/11/2006 2:51:37 PMPDONE
Trevin ###-####//please call 45 min - 1 hr to meet you there talked about new service and putting j-box in attic, clean up where old panel was, if sub panel, change range and dryer to 4 wire, may do additional work
ELE06-02887 Electrical Rough-In10/11/200610/11/200610/11/2006 2:20:40 PMPPASS
Scheduled by a contractor via Hello! on 10/11/2006 at 10:17:19 AM. Contact: ###-####. front lights ok to cover (soffit)
ELE06-02570 ELE-Aging Inspection10/11/200610/11/200610/11/2006 1:35:24 PM DONE
see final
ELE06-02570 Final10/11/200610/11/200610/11/2006 1:34:56 PMPPASS
called, looked at sign, ok to final
ELE06-02887 Permanent Service10/11/200610/11/200610/11/2006 1:24:49 PMPPASS
Scheduled by a contractor via Hello! on 10/11/2006 at 10:16:40 AM. Contact: ###-####. p/s u/g n ok, gold sticker on 600A disconnect inside bldg
ELE06-03707 Electrical Rough-In10/11/200610/11/200610/11/2006 12:49:30 PMPFAIL
Don; Phone #: ###-#### go thru side gate on east side to addn. Internet Inspection Request from: Cathy Weisshaupt called, left corr notice, nec 300.4(A)&(D) edge of bored holes and nm cable shall be 1 1/4" from edge of framing members, 250.86 metal enclosures shall be grounded, 110.12(C) there shall be no damaged parts (nm west side up high), BCC all make-up shall be done
ELE06-03776 Electrical Rough-In10/10/200610/11/200610/11/2006 11:48:47 AMAPASS
Shane; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt walls only ok to cover
ELE06-02513 Electrical Rough-In10/10/200610/11/200610/11/2006 10:13:54 AMACANC
call John for access so he can meet you; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles wrong type insp request, see rip
ELE06-03773 Electrical Rough-In10/11/200610/11/200610/11/2006 10:12:42 AMAPASS
Phone #: ###-#### Internet Inspection Request from: Clyde Logan walls only ok to cover
ELE06-03773 Final10/11/200610/11/200610/11/2006 10:11:42 AMACANC
Phone #: ###-#### Internet Inspection Request from: Clyde Logan see ri
ELE06-02513 Rough-In Permanent Service10/11/200610/11/200610/11/2006 10:04:38 AMPPASS
call John for access so he can meet you; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles told owner to add 1 recpt downstairs, ric ok, p/s o/h n ok
ELE06-02921 Electrical Rough-In10/10/200610/11/200610/11/2006 9:08:08 AMAPASS
mike Note: ceiling; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles ok to finish cover clg
ELE06-03724 Conference10/10/200610/11/200610/11/2006 8:48:05 AMADONE
Senad ###-####//please call 30 min prior to meet no work done, adding some repts, will call ltr
ELE06-03766 Rough-In Permanent Service10/10/200610/11/200610/11/2006 8:31:45 AMAFAIL
dino; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles called left corr notice, nec 210.52(A)(1) recpts shall be spaced so no point along wall is over 6' from outlet, 210.52(A)(2) recpt shall be installed in wall space over 2', 300.4(A) edge of bored hole shall be 1 1/4" from edge of framing member,404.8 center of breaker handle shall not be over 6'-7" above floor BCC approved set of plans shall be on job, address shall be posted