ELE06-00847
| Final | 10/11/2006 | 10/11/2006 | 10/11/2006 4:22:32 PM | P | PASS |
|
|
Garage code 2208; Phone #: ###-#### Internet Inspection Request from: Joe Thomas called contr about rev polarity on kitchen and dining ckt, ok to final
|
ELE06-00846
| Final | 10/11/2006 | 10/11/2006 | 10/11/2006 4:01:58 PM | P | PASS |
|
|
Garage code 2208; Phone #: ###-#### Internet Inspection Request from: Joe Thomas called contr to finish panel schedule, and add bkr lo for dw, ok to final
|
ELE06-02672
| Final | 10/9/2006 | 10/11/2006 | 10/11/2006 3:26:05 PM | P | NH |
|
|
Work performed by Matthew White. Internet Inspection Request from: Matt Santacruz called contr, left card
|
ELE04-00041
| Conference | 10/10/2006 | 10/11/2006 | 10/11/2006 2:51:37 PM | P | DONE |
|
|
Trevin ###-####//please call 45 min - 1 hr to meet you there talked about new service and putting j-box in attic, clean up where old panel was, if sub panel, change range and dryer to 4 wire, may do additional work
|
ELE06-02887
| Electrical Rough-In | 10/11/2006 | 10/11/2006 | 10/11/2006 2:20:40 PM | P | PASS |
|
|
Scheduled by a contractor via Hello! on 10/11/2006 at 10:17:19 AM. Contact: ###-####. front lights ok to cover (soffit)
|
ELE06-02570
| ELE-Aging Inspection | 10/11/2006 | 10/11/2006 | 10/11/2006 1:35:24 PM | | DONE |
|
|
see final
|
ELE06-02570
| Final | 10/11/2006 | 10/11/2006 | 10/11/2006 1:34:56 PM | P | PASS |
|
|
called, looked at sign, ok to final
|
ELE06-02887
| Permanent Service | 10/11/2006 | 10/11/2006 | 10/11/2006 1:24:49 PM | P | PASS |
|
|
Scheduled by a contractor via Hello! on 10/11/2006 at 10:16:40 AM. Contact: ###-####. p/s u/g n ok, gold sticker on 600A disconnect inside bldg
|
ELE06-03707
| Electrical Rough-In | 10/11/2006 | 10/11/2006 | 10/11/2006 12:49:30 PM | P | FAIL |
|
|
Don; Phone #: ###-#### go thru side gate on east side to addn. Internet Inspection Request from: Cathy Weisshaupt called, left corr notice, nec 300.4(A)&(D) edge of bored holes and nm cable shall be 1 1/4" from edge of framing members, 250.86 metal enclosures shall be grounded, 110.12(C) there shall be no damaged parts (nm west side up high), BCC all make-up shall be done
|
ELE06-03776
| Electrical Rough-In | 10/10/2006 | 10/11/2006 | 10/11/2006 11:48:47 AM | A | PASS |
|
|
Shane; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt walls only ok to cover
|
ELE06-02513
| Electrical Rough-In | 10/10/2006 | 10/11/2006 | 10/11/2006 10:13:54 AM | A | CANC |
|
|
call John for access so he can meet you; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles wrong type insp request, see rip
|
ELE06-03773
| Electrical Rough-In | 10/11/2006 | 10/11/2006 | 10/11/2006 10:12:42 AM | A | PASS |
|
|
Phone #: ###-#### Internet Inspection Request from: Clyde Logan walls only ok to cover
|
ELE06-03773
| Final | 10/11/2006 | 10/11/2006 | 10/11/2006 10:11:42 AM | A | CANC |
|
|
Phone #: ###-#### Internet Inspection Request from: Clyde Logan see ri
|
ELE06-02513
| Rough-In Permanent Service | 10/11/2006 | 10/11/2006 | 10/11/2006 10:04:38 AM | P | PASS |
|
|
call John for access so he can meet you; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles told owner to add 1 recpt downstairs, ric ok, p/s o/h n ok
|
ELE06-02921
| Electrical Rough-In | 10/10/2006 | 10/11/2006 | 10/11/2006 9:08:08 AM | A | PASS |
|
|
mike Note: ceiling; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles ok to finish cover clg
|
ELE06-03724
| Conference | 10/10/2006 | 10/11/2006 | 10/11/2006 8:48:05 AM | A | DONE |
|
|
Senad ###-####//please call 30 min prior to meet no work done, adding some repts, will call ltr
|
ELE06-03766
| Rough-In Permanent Service | 10/10/2006 | 10/11/2006 | 10/11/2006 8:31:45 AM | A | FAIL |
|
|
dino; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles called left corr notice, nec 210.52(A)(1) recpts shall be spaced so no point along wall is over 6' from outlet, 210.52(A)(2) recpt shall be installed in wall space over 2', 300.4(A) edge of bored hole shall be 1 1/4" from edge of framing member,404.8 center of breaker handle shall not be over 6'-7" above floor BCC approved set of plans shall be on job, address shall be posted
|