ELE07-03492
| Electrical Rough-In | 10/11/2007 | 10/11/2007 | 10/11/2007 3:27:45 PM | P | NR |
|
|
DAVE Phone #: ###-#### Internet Inspection Request from: Sean DeLacy ok to pour part of deck anop, center building area
|
ELE07-03491
| Final | 10/11/2007 | 10/11/2007 | 10/11/2007 2:43:40 PM | P | CANC |
|
|
DAVE TEMP POWER POLE Phone #: ###-#### Internet Inspection Request from: Sean DeLacy see t/s
|
ELE07-03491
| Temporary Service | 10/11/2007 | 10/11/2007 | 10/11/2007 1:58:22 PM | P | PASS |
|
|
DAVE TEMP POWER POLE Phone #: ###-#### Internet Inspection Request from: Sean DeLacy t/s o/h n ok
|
ELE07-03490
| Final | 10/11/2007 | 10/11/2007 | 10/11/2007 1:42:13 PM | P | CANC |
|
|
DAVE - TEMP POWER POLE Phone #: ###-#### Internet Inspection Request from: Sean DeLacy see t/s
|
ELE07-03490
| Temporary Service | 10/11/2007 | 10/11/2007 | 10/11/2007 1:41:38 PM | P | PASS |
|
|
DAVE - TEMP POWER POLE Phone #: ###-#### Internet Inspection Request from: Sean DeLacy t/s o/h n ok
|
ELE07-03241
| Electrical Rough-In | 10/11/2007 | 10/11/2007 | 10/11/2007 1:19:26 PM | P | FAIL |
|
|
ceiling and panel Phone #: ###-#### Internet Inspection Request from: Scott Abbott talked with contr, left correction notice to owner and elect. BCC no violations shall be retained, all ceiling tiles shall be removed for inspection, address shall be posted, NEC 110.12(C) there shall be no damaged parts that may adversely affect safe operation of equipment
|
ELE07-02237
| Final | 10/11/2007 | 10/11/2007 | 10/11/2007 10:38:41 AM | A | PASS |
|
|
met contractor, ok to final, people moved in, looked at receptacles that could get to only
|
ELE07-02775
| Final | 10/9/2007 | 10/11/2007 | 10/11/2007 10:36:42 AM | A | CANC |
|
|
jack - please call 1/2 hr prior to inspection Phone #: ###-#### wrong permit number, meant next door
|
ELE07-03486
| Electrical Rough-In | 10/10/2007 | 10/11/2007 | 10/11/2007 10:33:48 AM | A | PASS |
|
|
andy Phone #: ###-#### ri ok for a/c and kitchen can lites only
|
ELE07-03197
| Rough-In Permanent Service | 10/10/2007 | 10/11/2007 | 10/11/2007 9:18:29 AM | A | PASS |
|
|
rick Phone #: ###-#### corrections made, ric ok, p/s u/g n ok
|
ELE07-03481
| Electrical Rough-In | 10/11/2007 | 10/11/2007 | 10/11/2007 8:49:04 AM | P | FAIL |
|
|
lynn - underground Phone #: ###-#### called, left corr notice, nec 300.5 rnc u/g conduit shall be 24" under pavement, 352.26 there shall not be over 360 degree bends without pull point provided in rnc, BCC all u/g shall be inspected before cover
|
ELE07-03450
| Electrical Rough-In | 10/10/2007 | 10/11/2007 | 10/11/2007 8:28:16 AM | A | PASS |
|
|
We need electrical rough-in inspection and service inspection. Door code is 3072 Phone #: ###-#### Internet Inspection Request from: Alison Pennington ric ok for walls and hard lids only, addressing needs fixed before service ready
|
ELE07-02237
| Final | 10/9/2007 | 10/11/2007 | 10/10/2007 4:44:31 PM | A | CANC |
|
|
jack - please call 1/2 hr prior to inspection Phone #: ###-#### Inspection cancelled from web by: Patricia Smith
|