Inspections for the day of: Tuesday, October 11, 2011.
Number of inspections: 13
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD11-02405 FIRE-Final Inspection10/7/201110/11/201110/11/2011 4:21:25 PMPFAIL
Repair all of the inoperative exit signs/emergency lights, add emergency lights in locations as discussed, verify occupant load signs as discussed, remove the lock from the custodial closet door. The master switch on the ice rink emergency lighting is ok with Scott as long as a trained individual is stationed at this switch during functions.
FIR11-00438 INSP-Final Inspection10/10/201110/11/201110/11/2011 3:34:42 PMPCANC
Meet in the B.25 print review room. Phone #: ###-#### >> Inspection requested via web by John Wheeler Inspection cancelled from web by: John Wheeler
FIR11-00138 INSP-Final Inspection10/10/201110/11/201110/11/2011 3:34:40 PMPCANC
Meet in the B.25 print review room. Phone #: ###-#### >> Inspection requested via web by John Wheeler Inspection cancelled from web by: John Wheeler
BLD11-02005 FIRE-Final Inspection10/11/201110/11/201110/11/2011 2:22:05 PMPPASS
life safety passed
BLD11-00609 FIRE-Final Inspection10/11/201110/11/201110/11/2011 1:57:09 PMPFAIL
Provide sticker at main exit, provide exit signs as shown on the city approved plans, remove deadbolts from the east facing exit doors, and provide sprinkler modifications for the rooms with no sprinkler protection.
FIR11-00548 INSP-Final Inspection10/11/201110/11/201110/11/2011 11:42:52 AMPPASS
permit finaled
BLD11-02370 FIRE-Final Inspection10/6/201110/11/201110/11/2011 11:26:04 AMAFAIL
Remove the thumbturn deadbolt at the main exit. Keyed is ok on egress side. Per phone conversation with the fire alarm plan reviewer the existing fire alarm system is ok.
BLD11-00836 FIRE-Conference10/11/201110/11/201110/11/2011 9:59:22 AMADONE
Romeo Gervais and I met with Chad and Rich Raimondi, with Bishop Kelly, about the need for protection of both the fire sprinkler and fire alarm systems that are exposed to the elements. It was agreed that steps would be taken starting today and completed by the end of the week. Chad said he would follow up with me later in the week at which time I will perform a courtesy inspection.
FIR11-00299 INSP-Conference10/11/201110/11/201110/11/2011 9:53:31 AMADONE
Romeo Gervais and I met with Chad and Rich Raimondi, with Bishop Kelly, about the need for protection of both the fire sprinkler and fire alarm systems that are exposed to the elements. It was agreed that steps would be taken starting today and completed by the end of the week. Chad said he would follow up with me later in the week at which time I will perform a courtesy inspection.
BLD10-02870 FIRE-Final Inspection10/10/201110/11/201110/11/2011 9:47:18 AMAPART
A temporary occupancy was given until the Opticon has been provided for the fire dept access gate on the south side of the building.
FIR11-00382 INSP-Final Inspection10/10/201110/11/201110/11/2011 9:46:22 AMAPASS
Permit finaled
BLD11-02423 FIRE-Final Inspection10/10/201110/11/201110/11/2011 9:46:02 AMAFAIL
Provide door hardware as discussed with Jim Storey and provide suite number.
BLD11-01844 FIRE-Final Inspection10/10/201110/11/201110/11/2011 7:46:01 AMAFAIL
My contact, Kevin, did not know where the correct breakers were for the emergency lights /exit signs. No testing was performed. Will need to be rescheduled.