BLD11-02405
| FIRE-Final Inspection | 10/7/2011 | 10/11/2011 | 10/11/2011 4:21:25 PM | P | FAIL |
|
|
Repair all of the inoperative exit signs/emergency lights, add emergency lights in locations as discussed, verify occupant load signs as discussed, remove the lock from the custodial closet door. The master switch on the ice rink emergency lighting is ok with Scott as long as a trained individual is stationed at this switch during functions.
|
FIR11-00438
| INSP-Final Inspection | 10/10/2011 | 10/11/2011 | 10/11/2011 3:34:42 PM | P | CANC |
|
|
Meet in the B.25 print review room. Phone #: ###-#### >> Inspection requested via web by John Wheeler Inspection cancelled from web by: John Wheeler
|
FIR11-00138
| INSP-Final Inspection | 10/10/2011 | 10/11/2011 | 10/11/2011 3:34:40 PM | P | CANC |
|
|
Meet in the B.25 print review room. Phone #: ###-#### >> Inspection requested via web by John Wheeler Inspection cancelled from web by: John Wheeler
|
BLD11-02005
| FIRE-Final Inspection | 10/11/2011 | 10/11/2011 | 10/11/2011 2:22:05 PM | P | PASS |
|
|
life safety passed
|
BLD11-00609
| FIRE-Final Inspection | 10/11/2011 | 10/11/2011 | 10/11/2011 1:57:09 PM | P | FAIL |
|
|
Provide sticker at main exit, provide exit signs as shown on the city approved plans, remove deadbolts from the east facing exit doors, and provide sprinkler modifications for the rooms with no sprinkler protection.
|
FIR11-00548
| INSP-Final Inspection | 10/11/2011 | 10/11/2011 | 10/11/2011 11:42:52 AM | P | PASS |
|
|
permit finaled
|
BLD11-02370
| FIRE-Final Inspection | 10/6/2011 | 10/11/2011 | 10/11/2011 11:26:04 AM | A | FAIL |
|
|
Remove the thumbturn deadbolt at the main exit. Keyed is ok on egress side. Per phone conversation with the fire alarm plan reviewer the existing fire alarm system is ok.
|
BLD11-00836
| FIRE-Conference | 10/11/2011 | 10/11/2011 | 10/11/2011 9:59:22 AM | A | DONE |
|
|
Romeo Gervais and I met with Chad and Rich Raimondi, with Bishop Kelly, about the need for protection of both the fire sprinkler and fire alarm systems that are exposed to the elements. It was agreed that steps would be taken starting today and completed by the end of the week. Chad said he would follow up with me later in the week at which time I will perform a courtesy inspection.
|
FIR11-00299
| INSP-Conference | 10/11/2011 | 10/11/2011 | 10/11/2011 9:53:31 AM | A | DONE |
|
|
Romeo Gervais and I met with Chad and Rich Raimondi, with Bishop Kelly, about the need for protection of both the fire sprinkler and fire alarm systems that are exposed to the elements. It was agreed that steps would be taken starting today and completed by the end of the week. Chad said he would follow up with me later in the week at which time I will perform a courtesy inspection.
|
BLD10-02870
| FIRE-Final Inspection | 10/10/2011 | 10/11/2011 | 10/11/2011 9:47:18 AM | A | PART |
|
|
A temporary occupancy was given until the Opticon has been provided for the fire dept access gate on the south side of the building.
|
FIR11-00382
| INSP-Final Inspection | 10/10/2011 | 10/11/2011 | 10/11/2011 9:46:22 AM | A | PASS |
|
|
Permit finaled
|
BLD11-02423
| FIRE-Final Inspection | 10/10/2011 | 10/11/2011 | 10/11/2011 9:46:02 AM | A | FAIL |
|
|
Provide door hardware as discussed with Jim Storey and provide suite number.
|
BLD11-01844
| FIRE-Final Inspection | 10/10/2011 | 10/11/2011 | 10/11/2011 7:46:01 AM | A | FAIL |
|
|
My contact, Kevin, did not know where the correct breakers were for the emergency lights /exit signs. No testing was performed. Will need to be rescheduled.
|