Inspections for the day of: Tuesday, October 11, 2016.
Number of inspections: 13
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTom Saunders
TitleELE-INSPECTOR
Phone #208-794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE16-02590 Electrical Rough-In10/10/201610/11/201610/11/2016 2:47:16 PMPPASS
Wall / ceiling inspection please.
Tuesday afternoon.

Please call Dylan Pierce with questions ###-#### Phone #: ###-#### Inspection requested via web by Darren Larsen

walls and lids ok to cover as marked on plans
ELE16-02875 Final10/11/201610/11/201610/11/2016 1:48:35 PMPFAIL
Phone #: ###-#### Inspection requested via web by daniel bibikov

.....breaker lock outs need installed on water heater and hood....lockout on d/w needs installed properly...exposed wire above hood needs removed or safed off
ESC16-00789 Site Preparation10/11/201610/11/201610/11/2016 1:07:48 PMPPASS
ok to final
ELE16-03281 Electrical Rough-In10/10/201610/11/201610/11/2016 1:01:09 PMACANC
Jeff// please call 30 minutes prior Phone #: ###-####

wrong inspection...ment to do conference
ELE16-03281 Conference10/11/201610/11/201610/11/2016 1:00:24 PMADONE
Jeff// please call 30 minutes prior Phone #: ###-####

discussed wiring of pole barn....required protection of wiring, gfi protection of outlets, service requirements, grounding, wire protection in chase, bond bushing, seperation of grounds and neutrals
ELE16-03235 Rough-In Permanent Service10/10/201610/11/201610/11/2016 11:18:24 AMAPASS
Phone #: ###-#### Inspection requested via web by Bob Glenn

ok to cover
p/s u/g n ok
ELE16-02379 Final10/11/201610/11/201610/11/2016 10:32:23 AMAPASS
corrections made....ok to final
ELE16-02378 Final10/11/201610/11/201610/11/2016 10:31:36 AMAPASS
corrections made...ok to final
ELE16-02377 Final10/11/201610/11/201610/11/2016 10:30:58 AMAPASS
corrections made....ok to final
ELE16-02375 Final10/10/201610/11/201610/11/2016 10:15:53 AMAPASS
would like call ahead; Justin Phone #: ###-####

corrections made....ok to final
ELE16-03287 Final10/10/201610/11/201610/11/2016 9:11:33 AMACANC
Exterior panel only for idaho power Phone #: ###-#### Inspection requested via web by John Harvey

wrong inspection
ELE16-03287 Permanent Service10/11/201610/11/201610/11/2016 9:11:12 AMAFAIL
Exterior panel only for idaho power Phone #: ###-#### Inspection requested via web by John Harvey

2nd ground rod needs added
grounding electrode conductor shall be attached with an approved connnector
ELE16-02558 Final10/10/201610/11/201610/11/2016 8:18:32 AMAPASS
ok to final