Inspections for the day of: Thursday, October 11, 2018.
Number of inspections: 8
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE18-03477 Final10/11/201810/11/201810/11/2018 3:49:25 PMPFAIL
Phone #: ###-#### Inspection requested via web by Bryan Atkins
BCC 4 05 32- No code violation shall be retained. 210.8(B)- Receptacle outlets located with in 6' of a sink shall have GFCI protection. Receptacle outlets located with in 6' of a new sink in exam rooms.
314.25- Open boxes shall have covers.
ELE18-03900 Temporary Service10/11/201810/11/201810/11/2018 3:12:23 PMPPASS
Inspection requested via web by TOM BICANDI
t/s o/h n ok
ELE18-02780 Electrical Rough-In10/11/201810/11/201810/11/2018 2:25:14 PMPPASS
open wall in show room Phone #: ###-#### Inspection requested via web by Angela Stears
Eye glass display wall rough in ok cover
ELE18-02777 Final10/11/201810/11/201810/11/2018 1:42:47 PMPPASS
Phone #: ###-#### Inspection requested via web by Ryan Wake Final ok
ELE18-03898 Final10/10/201810/11/201810/11/2018 12:27:17 PMAPART
Phone #: ###-#### Inspection requested via web by Ron Zimmerman
210.8- GFCI protection on all 120 volt receptacles with in 6' of a sink and outdoors. Southeast entry has outdoor receptacle near it and end of bar has receptacle with in 6' of a sink.
314.20- All boxes installed in a combustible wall material shall be flush with combustible surface, D-5 circuit near dining room and D-11 circuit near panel wall.
Contractor to correct prior to customer access. Signed TCO partial final ok
ELE18-03892 Conference10/10/201810/11/201810/11/2018 10:45:20 AMAPASS
after 9am- Etta Phone #: ###-####
Owners father doing work, Discussed receptacle layouts includes upstair rail and fixed panel of sliding doors, each bathroom on dedicated 20 amp circuits, grounding electrode bent over to interior of crawl space, max height of breaker handles, secure support of NM cable, pamphlet given
ELE18-03900 Temporary Service10/10/201810/11/201810/11/2018 9:53:45 AMAFAIL
Overhead temp pole Phone #: ###-#### Inspection requested via web by TOM BICANDI
590.6(B)- All temp power receptacle outlets other than 120 volt shall have GFCI protection.
Standard 2-pole 40 installed.
ELE18-03827 Rough-In Permanent Service10/10/201810/11/201810/11/2018 8:40:40 AMAPASS
Phone #: ###-#### Inspection requested via web by Darryn Coburn
Rough in ok cover p/s u/g n ok