ELE17-02434
| DOC - Permit Expired | 10/11/2019 | 10/11/2019 | 10/11/2019 3:04:35 PM | P | PASS |
|
|
Doc expire OK
|
ELE19-03829
| Electrical Rough-In | 10/10/2019 | 10/11/2019 | 10/11/2019 2:56:17 PM | P | PASS |
|
|
Uffer ground inspection Contact Shawn Evins Thank you Phone #: ###-#### Inspection requested via web by Cathy Duchek Concrete encased electrode rough in ok cover
|
ELE19-02715
| Electrical Rough-In | 10/10/2019 | 10/11/2019 | 10/11/2019 2:17:45 PM | P | PASS |
|
|
Bill Peace is contact at ###-####. Phone #: ###-#### Inspection requested via web by Debby Pierce Level 4 phase 2- Kitchenette, records rm, storage rm, and small eastern rm wall rough in ok cover.
|
ELE19-03464
| Permanent Service | 10/11/2019 | 10/11/2019 | 10/11/2019 2:16:07 PM | P | PASS |
|
|
Installation is exempt from Title 54 Chapter 10 permitting and inspection requirements. Disconnect does not meet NEC 230.70(A)(1). Utility has exclusive control to energize installation. Include any other code violations 250.50- All Grounding electrodes as described in 250.52(A)(1) thru (A)(7) that are present shall be used as grounding electrode system. #6 bare copper conductor run down pole and coiled at bottom of pole is not described in article listed. p/s o/h n ok
|
ELE19-03741
| Final | 10/11/2019 | 10/11/2019 | 10/11/2019 1:40:17 PM | A | NH |
|
|
Contact is Dan Bora Phone #: ###-#### Inspection requested via web by Scott Campbell Called contact to find area work was performed, no answer, left message, in building for 20 minutes no return call. Must recall
|
ELE19-03929
| Rough-In Permanent Service | 10/10/2019 | 10/11/2019 | 10/11/2019 11:44:47 AM | A | FAIL |
|
|
Thank you :) Phone #: ###-#### Inspection requested via web by Charles Davis 110.3- Family room recessed can junction box cover shall seat tight to box. 210.52(D)- A receptacle outlet shall be installed adjacent to each basin in bathrooms. Master bath has 2 basins. 210.52(E)(3)- Patios or deck accessible form inside house shall have a receptacle outlet installed within its perimeter. Back patio. 300.4- Nail plate above east front garage light. 334.30- Secure NM cable below receptacle in garage near door to house. OK to foam seal.
|
ELE19-03302
| Conference | 10/10/2019 | 10/11/2019 | 10/11/2019 10:00:36 AM | A | DONE |
|
|
Please call in advance so I can meet you. Phone #: ###-#### Inspection requested via web by Rex Boyles Discussed mast height and work clearance for replacement of service without disconnecting means for feeds to sub panels. Disconnects woll be in place with new service.
|
ELE19-03918
| Temporary Service | 10/10/2019 | 10/11/2019 | 10/11/2019 9:45:08 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by David Nelson t/s u/g n ok
|
ELE19-02875
| Final | 10/10/2019 | 10/11/2019 | 10/11/2019 9:10:40 AM | A | FAIL |
|
|
access: 4141 Phone #: ###-#### Inspection requested via web by David Nelson 210.8- All GFCi devices shall be located in a readily accessible location. Garage heater receptacle. 422.30- Appliances shall have a disconnecting means. 110.25 lockouts acceptacle. Microwave.
|