Inspections for the day of: Wednesday, October 12, 2005.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE05-03180 Electrical Rough-In10/11/200510/12/200510/12/2005 4:45:07 PMPFAIL
Scheduled by a contractor via Hello! on 10/11/2005 at 4:07:41 PM. talked with contr, gave ok to cover front half clg, left corr notice for back 1/2 clg. 110.26(F)(1)(b) protection shall be installed to avoid damage to elect equip in dedicated space. Also wrote corr notice to Bld05-00311- nec 800.24 Comm cables shall be installed in workmanlike manner and supported by straps,staples, hangers or similar fittings and installed so as to not damage the cable.
ELE05-00855 Electrical Rough-In10/12/200510/12/200510/12/2005 4:38:39 PMPPART
CONTACT: LYLE DEAN 2ND FLOOR INSPECTION; Phone #: ###-#### Internet Inspection Request from: Deb McCoy 2nd floor ramp ok to cover anop
ELE05-03719 Temporary Service10/12/200510/12/200510/12/2005 4:37:51 PMPFAIL
###-#### - allen called contr, left corr notice, 312.5 gec shall have abrasion prot, 110.12(C) there shall be no broken parts,BCC job id sticker shall be posted.
ELE05-03707 Electrical Rough-In10/12/200510/12/200510/12/2005 2:09:18 PMPPART
jeremiah; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa 2nd floor walls only ok to cover anop. hold over panels and chases till ltr.
ELE05-03645 Electrical Rough-In10/12/200510/12/200510/12/2005 1:54:25 PMPPASS
CONTACT: SHANE KORTE; Phone #: ###-#### Internet Inspection Request from: Deb McCoy ric ok, p/s u/g n ok
ELE05-03446 Final10/12/200510/12/200510/12/2005 12:31:27 PMPFAIL
###-#### - doug called, left message, left corr notice, 330.24(B) mc cable shall be strapped within 12" of box and 6' intervals, 408.4 panel schedule not explicit, BCC need to see ceiling
ELE05-03624 Final10/12/200510/12/200510/12/2005 11:37:01 AMACANC
inspect front soffit for cover; Phone #: ###-#### Internet Inspection Request from: Ryan Christensen 336 did
ELE05-02224 Electrical Rough-In10/11/200510/12/200510/12/2005 9:20:09 AMAPART
Scheduled by a contractor via Hello! on 10/11/2005 at 2:45:18 PM. Contact: ###-####. part of kitchen, bar, and dining room ok. will finish later. (Done as part final.)
ELE05-03661 Electrical Rough-In10/11/200510/12/200510/12/2005 9:15:55 AMAPART
Scheduled by a contractor via Hello! on 10/11/2005 at 2:44:14 PM. Contact: ###-####. walls anop only ok to cover. willsee more later
ELE04-04022 Electrical Rough-In10/11/200510/12/200510/12/2005 9:14:50 AMAPART
Scheduled by a contractor via Hello! on 10/11/2005 at 2:43:11 PM. Contact: ###-####. stair well walls ok to cover anop