BLD05-01657
| FIRE-Final Inspection | 10/12/2005 | 10/12/2005 | 10/12/2005 3:54:10 PM | P | FAIL |
|
|
Mount fire extinguisher with current tag on the wall along a normal path of travel as discussed, relocate suite address numbers from their currrent location on the bottom of the door to an area visible at all times (such as at the top of the door or above).
|
FIR05-00566
| INSP-Final Inspection | 10/11/2005 | 10/12/2005 | 10/12/2005 12:59:11 PM | A | FAIL |
|
|
The hood suppression system operated correctly under test conditions. However, the manual pulls are obstructed from view and operation when the adjacent storage room door is in the fully open position- need to relocate pulls or provide automatic door closure as discussed. Also, two cooking burners on the 9 gallon system exceed the 4' limit to the hood edge, need to raise height so the cooking surface is within allowable limits.
|