FIR06-00686
| INSP-Sprinkler Rough-in | 10/12/2006 | 10/12/2006 | 10/13/2006 11:20:18 AM | P | PART |
|
|
Sprinkler piping is ok to cover but one additional head is needed in the front display area due to a horizontal obstruction and the wood supporting the hvac unit is a problem
|
FIR06-00137
| INSP-Sprinkler Rough-in/Hydro | 10/12/2006 | 10/12/2006 | 10/12/2006 3:56:25 PM | P | PASS |
|
|
Underground and overhead hydro tests passed.
|
BLD05-03298
| FIRE-Final Inspection | 10/12/2006 | 10/12/2006 | 10/12/2006 3:17:19 PM | P | FAIL |
|
|
Need fire alarm permits finaled first. The fire alarm permit was failed.
|
BLD05-00916
| FIRE-Final Inspection | 10/12/2006 | 10/12/2006 | 10/12/2006 3:15:15 PM | P | PART |
|
|
A temporary occupancy was given with dave hannimans permission until the knox box is provided.
|
BLD06-01978
| FIRE-Final Inspection | 10/12/2006 | 10/12/2006 | 10/12/2006 3:14:54 PM | P | PART |
|
|
A temporary occupancy was given with dave hannimans permission until the knox box is provided.
|
FIR06-00106
| INSP-Final Inspection | 10/12/2006 | 10/12/2006 | 10/12/2006 3:14:08 PM | P | FAIL |
|
|
Apparently the general contractor called in the inspection without the fire alarm contractors knowledge. I called the fire alarm contractor and got no responce. No inspection performed.
|
FIR05-00644
| INSP-Sprinkler Rough-in | 10/11/2006 | 10/12/2006 | 10/12/2006 3:12:07 PM | A | PASS |
|
|
The club house branchline piping located below the hard lids but above the lay ceiling passed. Prior to cover the armovers will need to be inspected. I notified the sprinkler contractor that the fireplace area and the stairwells will need to be opened up for verification that the combustible areas have met the exceptions as stated in NFPA 13 for areas not requiring sprinklers. Another potential problem are the combustible eave pockets.
|
FIR06-00627
| INSP-Final Inspection | 10/12/2006 | 10/12/2006 | 10/12/2006 2:06:24 PM | P | PASS |
|
|
permit finaled
|
FIR06-00603
| INSP-Sprinkler Rough-in | 10/11/2006 | 10/12/2006 | 10/12/2006 1:35:46 PM | P | PASS |
|
|
Piping is ok to cover but depth of bury will have to be checked at final. Per Brian it will be ok due to landscaping. Top of pipe is 4'-9" below the building foundation and measures 14' off the face of the building. The 4'-6" will be verified.
|
BLD06-02022
| FIRE-Final Inspection | 10/11/2006 | 10/12/2006 | 10/12/2006 12:00:12 PM | P | FAIL |
|
|
mount fire extinguisher, provide missing canopies, provide hardware for office door and remove thumbturn from restroom door.
|
FIR06-00485
| FIR-Aging Inspection | 10/12/2006 | 10/12/2006 | 10/12/2006 10:45:02 AM | | NR |
|
|
work is in progress per Jeff
|
FIR06-00673
| INSP-Sprinkler Rough-in | 10/11/2006 | 10/12/2006 | 10/12/2006 10:29:48 AM | A | PASS |
|
|
Sprinkler rough-in passed.
|