Inspections for the day of: Monday, October 12, 2009.
Number of inspections: 6
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD09-00273 FIRE-Final Inspection10/12/200910/12/200910/12/2009 3:36:44 PMPPASS
life safety passed
BLD09-01563 FIRE-Final Inspection10/12/200910/12/200910/12/2009 2:12:38 PMPPASS
LIfe safety passed.
FIR09-00561 INSP-Sprinkler Rough-in/Hydro10/9/200910/12/200910/12/2009 11:46:28 AMAFAIL
Todays inspection was for the overhead hydro test which failed.
BLD09-01592 FIRE-Final Inspection10/9/200910/12/200910/12/2009 11:44:41 AMAFAIL
Overhead sprinkler coverage has been blocked by the new roll up door. Sprinkler coverage with the associated permit is required prior to sign off. Also the existing fire sprinkler system annual inspection is past due.
BLD09-01756 FIRE-Final Inspection10/9/200910/12/200910/12/2009 10:07:40 AMAFAIL
Provide a maximum occupant load sign and provide verification of emergency lighting as discussed.
BLD09-00273 FIRE-Final Inspection10/9/200910/12/200910/12/2009 9:30:46 AMAFAIL
provide indicator at the main exit