Inspections for the day of: Wednesday, October 12, 2011.
Number of inspections: 14
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR11-00072 INSP-Final Inspection10/12/201110/12/201110/12/2011 4:05:53 PMPFAIL
Per Leo, this is a Gaylord system. Per last correspondence with Ansul, all plenum spaces in Gaylord hoods are required to be protected with nozzels. This supression system has not been installed in accordance with those requirements. Forwarded an email to Leo from Ansul/Tyco corporation. No inspection performed.
FIR11-00414 INSP-Sprinkler Rough-in/Hydro10/12/201110/12/201110/12/2011 4:02:51 PMPCANC
Cancelled. Overbooked - rescheduled for tomorrow.
BLD11-01512 FIRE-Conference10/11/201110/12/201110/12/2011 3:08:52 PMADONE
Met with the owner, architect and the building inspector about scope of work changes and a possible temporary occupancy.
BLD11-00416 FIRE-Final Inspection10/12/201110/12/201110/12/2011 3:07:49 PMPCANC
Overbooked. Rescheduled for tomorrow.
BLD11-00416 FIRE-Final Inspection10/12/201110/12/201110/12/2011 3:07:12 PMPCANC
Duplicate inspection
BLD11-02022 FIRE-Final Inspection10/11/201110/12/201110/12/2011 2:18:02 PMAPASS
life safety passed
BLD11-01126 FIRE-Final Inspection10/11/201110/12/201110/12/2011 2:17:06 PMAPASS
life safety passed
FIR11-00138 INSP-Final Inspection10/11/201110/12/201110/12/2011 2:13:29 PMPPASS
permit finaled
FIR11-00438 INSP-Final Inspection10/11/201110/12/201110/12/2011 2:12:09 PMPPASS
permit finaled
BLD11-00885 FIRE-Final Inspection10/12/201110/12/201110/12/2011 11:45:53 AMPPASS
life safety passed
BLD11-01386 FIRE-Final Inspection10/12/201110/12/201110/12/2011 10:42:33 AMPFAIL
The sticker needs to be provided at the main exit, deadbolt removed and singel action hardware at the rear exit and corrected floor plans submitted to plan review.
FIR11-00399 INSP-Final Inspection10/11/201110/12/201110/12/2011 9:49:48 AMAFAIL
Signals are now being reported correctly. As-builts/Intelipro information was not provided as requested by plan review.
FIR11-00341 INSP-Sprinkler Rough-in10/11/201110/12/201110/12/2011 9:04:04 AMAPASS
See the area with todays date where sprinkler piping can be covered.
BLD11-01069 FIRE-Final Inspection10/11/201110/12/201110/12/2011 8:04:33 AMAFAIL
Drew Phone #: ###-#### Left message on the contacts voice mail. Stopped at the buisiness and three gentleman stated that Drew was not in yet. No inspection was performed.