BLD16-04278
| FIRE-Final Inspection | 10/11/2017 | 10/12/2017 | 10/12/2017 1:47:23 PM | P | PASS |
|
|
Life safety passed
Kelly Phone #: ###-####
|
BLD17-02893
| FIRE-Final Inspection | 10/12/2017 | 10/12/2017 | 10/12/2017 1:36:39 PM | P | CANC |
|
|
To be rescheduled for tomorrow due to the fire alarm not being ready and I need verification from an engineer that the smoke evac system is still functional/installed as designed.
Troy Phone #: ###-####
|
FIR17-00539
| INSP-Sprinkler Rough-in | 10/11/2017 | 10/12/2017 | 10/12/2017 12:45:58 PM | P | PASS |
|
|
Rough-in passed. Piping can be covered.
|
FIR16-00821
| INSP-Sprinkler Rough-in | 10/12/2017 | 10/12/2017 | 10/12/2017 12:07:49 PM | P | PASS |
|
|
Remaining piping in the east most building can be covered. Insulation has been added to the combustible concealed spaces.
|
BLD16-03633
| FIRE-Final Inspection | 10/12/2017 | 10/12/2017 | 10/12/2017 12:07:00 PM | P | FAIL |
|
|
Repair the exit sign/emergency light and remove the thumb turn deadbolt at the exit door.
|
FIR17-00365
| INSP-Supply line flush | 10/12/2017 | 10/12/2017 | 10/12/2017 11:44:22 AM | P | PASS |
|
|
Underground supply line flush passed
|
FIR17-00433
| INSP-Supply line flush | 10/11/2017 | 10/12/2017 | 10/12/2017 11:44:00 AM | P | CANC |
|
|
Wrong permit number called in
|
FIR17-00433
| INSP-Sprinkler Rough-in | 10/11/2017 | 10/12/2017 | 10/12/2017 11:28:42 AM | A | PASS |
|
|
The earth quake bracing has been corrected. The branchline siesmic restraints have been added and the east facing extended coverage dry sidewall has been piped. Lower level piping can be covered except where the piping penatrates out to the front entry canopy
|
FIR17-00587
| INSP-Sprinkler Rough-in | 10/11/2017 | 10/12/2017 | 10/12/2017 10:17:56 AM | A | PART |
|
|
Underground supply piping is ok to bury except for the stub-in to the building which still needs a thrust block poured for the "in building riser".
|
FIR17-00568
| INSP-Sprinkler Rough-in | 10/11/2017 | 10/12/2017 | 10/12/2017 9:02:36 AM | A | PASS |
|
|
Rough-in passed. Piping can be covered.
|
BLD17-03165
| FIRE-Final Inspection | 10/11/2017 | 10/12/2017 | 10/12/2017 8:29:09 AM | A | PASS |
|
|
Life safety passed.
Please call Sid ###-####
|
BLD17-02257
| FIRE-Final Inspection | 10/11/2017 | 10/12/2017 | 10/12/2017 8:28:45 AM | A | PASS |
|
|
Life safety passed
Dave Phone #: ###-####
|
BLD17-01782
| FIRE-Final Inspection | 10/11/2017 | 10/12/2017 | 10/12/2017 8:28:20 AM | A | PASS |
|
|
life safety passed
Dave Phone #: ###-####
|
BLD16-04227
| FIRE-Final Inspection | 10/11/2017 | 10/12/2017 | 10/12/2017 8:27:58 AM | A | PASS |
|
|
Life safety passed.
Dave Phone #: ###-####
|
FIR17-00511
| INSP-Final Inspection | 10/11/2017 | 10/12/2017 | 10/12/2017 8:13:54 AM | A | PASS |
|
|
Permit finaled
|
FIR17-00227
| INSP-Final Inspection | 10/10/2017 | 10/12/2017 | 10/12/2017 7:39:32 AM | A | PASS |
|
|
Permit finaled.
|
BLD16-02954
| FIRE-Final Inspection | 10/11/2017 | 10/12/2017 | 10/11/2017 2:17:49 PM | A | PASS |
|
|
life safety passed
Tim Phone #: ###-####
|
BLD16-02953
| FIRE-Final Inspection | 10/11/2017 | 10/12/2017 | 10/11/2017 2:17:26 PM | A | PASS |
|
|
life safety passed
Tim Phone #: ###-####
|
BLD16-01617
| FIRE-Final Inspection | 10/11/2017 | 10/12/2017 | 10/11/2017 2:17:04 PM | A | PASS |
|
|
life safety passed
Tim Phone #: ###-####
|
BLD16-02952
| FIRE-Final Inspection | 10/11/2017 | 10/12/2017 | 10/11/2017 2:16:38 PM | A | PASS |
|
|
Life safety passed.
Tim Phone #: ###-####
|
BLD16-02951
| FIRE-Final Inspection | 10/11/2017 | 10/12/2017 | 10/11/2017 2:16:12 PM | A | PASS |
|
|
Life safety passed
Tim Phone #: ###-####
|
BLD16-02948
| FIRE-Final Inspection | 10/11/2017 | 10/12/2017 | 10/11/2017 2:15:50 PM | A | PASS |
|
|
Life safety passed.
Tim Phone #: ###-####
|
BLD16-02950
| FIRE-Final Inspection | 10/11/2017 | 10/12/2017 | 10/11/2017 2:15:27 PM | A | PASS |
|
|
Life safety passed.
Tim Phone #: ###-####
|
BLD16-02949
| FIRE-Final Inspection | 10/11/2017 | 10/12/2017 | 10/11/2017 2:15:07 PM | A | PASS |
|
|
Life safety passed.
Tim Phone #: ###-####
|