Inspections for the day of: Tuesday, October 13, 1998.
Number of inspections: 6
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRick Jackson
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD98-00541 INSP-Final Inspection10/12/199810/13/199810/13/1998 12:00:00 AMAPASS
Scheduled by Hello!. received med gas certification - occ approved
BLD98-01191 INSP-Sprinkler Rough-in/Hydro10/13/199810/13/199810/13/1998 12:00:00 AMAPART
underground hydro okay. sway bracing needed as most areas not complete. okay to cover in 1st floor of bathroom areas (fab area)
BLD98-01424 INSP-Final Inspection10/12/199810/13/199810/13/1998 12:00:00 AMAFAIL
Scheduled by Hello!. Contact phone is [4331105]. extinguisher needed and exit unobstructed
BLD97-01368 INSP-Sprinkler Rough-in/Hydro10/13/199810/13/199810/13/1998 12:00:00 AMPFAIL
HAROLD ###-#### pizza exhaust duct not ready for cover; areas not sprinklered not receiving hard lid
BLD97-02083 INSP-Sprinkler Rough-in/Hydro10/13/199810/13/199810/13/1998 12:00:00 AMPFAIL
bathroom corridor not sprinklered; linen/mop closet not sprinklered; overspacing with sidewalls
BLD97-03173 INSP-Sprinkler Rough-in/Hydro10/13/199810/13/199810/13/1998 12:00:00 AMPPART
pat simons ###-#### fire r-in insp requested location for outside bell - northeast wall