Inspections for the day of: Monday, October 13, 2003.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRick Jackson
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR03-00382 FIR-Aging Inspection10/13/200310/13/200310/13/2003 12:00:00 AM PASS
FIR03-00529 INSP-Sprinkler Rough-in/Hydro10/10/200310/13/200310/13/2003 12:00:00 AMAPASS
eric; Phone #: ###-#### Internet Inspection Request from: Annette Moore okay to cover; insulation is in the space under the fireplace and head installed in concealed space around fireplace; draft stops okay; will need to test alarms and forward flow BFP; as-builts needed 10/13/2003 8:55:21 AM
BLD03-00798 FIRE-Alarm Testing10/9/200310/13/200310/13/2003 12:00:00 AMPFAIL
Scheduled by a contractor via Hello! on 10/9/2003 at 12:34:43 PM. Contact: ###-####. per Dave Miller the fire alarm panel will have to be upgraded or meet his timeline for upgrade as all of the relocatables are on one zone but aren't located in the same area; smoke detectors are overspaced; simplex pulls used to facilitate the tamper proof covers 10/13/2003 4:48:14 PM
FIR03-00303 INSP-Alarm Testing10/13/200310/13/200310/13/2003 12:00:00 AMPPASS
Phone #: ###-#### Internet Inspection Request from: Daniel Buccino battery calc's provided per plan review notes 10/13/2003 2:47:43 PM
FIR03-00460 INSP-Alarm Testing10/13/200310/13/200310/13/2003 12:00:00 AMPPASS
Phone #: ###-#### Internet Inspection Request from: Daniel Buccino
BLD03-00451 FIRE-Final Inspection10/13/200310/13/200310/13/2003 12:00:00 AMPPASS
ED; Phone #: ###-#### Internet Inspection Request from: Annette Moore
FIR03-00506 INSP-Final Inspection10/13/200310/13/200310/13/2003 12:00:00 AMPFAIL
Please Call 1 hour prior to arrival to arrange someone there.; Phone #: ###-#### Internet Inspection Request from: Trent Bice freezer on south side requires foam at penetration and canopy; replace flow switch cover; riser room obstructed with storage 10/13/2003 3:28:16 PM
FIR03-00480 INSP-Sprinkler Rough-in/Hydro10/13/200310/13/200310/13/2003 12:00:00 AMPPART
RICK; Phone #: ###-#### Internet Inspection Request from: Annette Moore verified hangers/straps in dayroom area and east side cells; okay to fireproof 10/13/2003 9:44:15 AM 10/13/2003 10:51:22 AM
FIR03-00204 INSP-Alarm Testing10/13/200310/13/200310/13/2003 12:00:00 AMPPASS
Scheduled by a contractor via Hello! on 10/13/2003 at 8:56:28 AM. Contact: ###-####.
BLD03-01105 FIRE-Final Inspection10/13/200310/13/200310/13/2003 12:00:00 AMPPASS
jeff; Phone #: ###-#### Internet Inspection Request from: Annette Moore
BLD02-02759 FIRE-Final Inspection10/13/200310/13/200310/13/2003 12:00:00 AMPPASS